background image

CAUTION: LENGTH OF FORKS MUST BE A MINIMUM OF

54" (when lifting from the compressor end of the
unit) and a MINIMUM OF 42" (when lifting from the
front or rear of the unit).

Remove the nesting brackets from the four corners on top of
the unit. All screws that are removed to take these brackets off
must be replaced on the unit.

CLEARANCES

All units require certain minimum clearances for proper opera-
tion and service. Refer to Figure 4 for these clearances.

WARNING: Do not permit overhanging structures or shrubs

to obstruct air discharge.

Additional height may be required for snow clearance if winter
operation is expected.

COMPRESSOR CRANKCASE HEATER

The compressor is equipped with a crankcase heater to pre-

vent refrigerant from mixing with crankcase oil during the

“OFF” cycle. The heaters will be energized when the com-

pressor is not running providing the unit disconnect switch is

closed.

CAUTION: Do not attempt to start the compressor without at

least eight hours of crankcase heat or compressor
damage will occur.

If a unit has just been installed or the unit disconnect switch has
been open for a long period of time, move the system switch on
the room thermostat to the “OFF” position before closing the
unit disconnect switch. Eight hours of crankcase heat are re-
quired to drive the liquid refrigerant out of the compressor bef-
ore the compressor can be started.

POWER AND CONTROL WIRING

Install electrical wiring in accordance with the latest National
Electrical Code (NFPA Standard No. 70) and/or local regula-

tions. The unit should be grounded in accordance with these

codes.

POWER WIRING

Check the voltage of the power supply against the data on

the unit nameplate. Check the size of the power wire, the

disconnect switch and the fuses against the data in Table 3.

NOTE: Copper conductors must be installed between the dis-

connect switch and the unit.

Refer to Figure 4 for the location of the power wire access

opening through the front of the unit. This opening will re-

quire a field-supplied conduit fitting.

The field-supplied disconnect switch must be suitable for an
outdoor location. Although it should be installed near the unit,
do NOT secure it to the unit cabinet.

Refer to Figure 3 for typical field wiring.

CONTROL WIRING

Refer to Figure 4 for the location of the control wire access
opening through the front of the unit.

Route the necessary low voltage control wires from terminal

block TB2 of the unit control box through this access open-

ing to the indoor unit and to the room thermostat. Refer to

Figure 3 for typical field wiring.

The room thermostat should be mounted about 5 feet above

the floor and located where it will be exposed to normal room

air circulation. Do not locate it on an outside wall, near a

supply air grille, or where it may be affected by sunlight

4

Unitary Products Group

035-16192-001-A-1001

O

O

O

O

O

O

O

O

O

O

FIG. 2 - TYPICAL RIGGING

5 ft.

MIN

DESCRIPTION

UNIT MODEL

EFB180

EFB240

Compressor

1

Rating - (Qty) Tons

(2) 7-1/2

(2) 10

Fans

Quantity

2

2

Diameter - inches

24

26

Blades/Pitch (°)

3/32

3/36

Nominal CFM

10862

11395

Fan Motors

2

HP

1

1

RPM

1100

1100

Rows Deep X Rows High

2 X 40

2 X 40

Finned Length - inches

130

130

Face Area - square feet

36.11

36.11

Tube(Copper) OD - inches

3/8

3/8

Fins (Aluminum) per inch

18

20

Holding Charge

(Sys 1 / Sys 2)

3

1-0/1-0

1-0/1-0

Operating Charge

(Sys  1 / Sys 2)

4

16-8/17-8 19-0/19-0

Shipping

970

1020

Operating

980

1040

1

These compressors are fully hermetic.

2

The ball bearing, 48 frame, single phase condenser fan motor have internal

protection and are directly connected to the condenser fins.  Motor rotation is
counterclockwise when viewing the lead end, which is opposite the shaft end.

3

The amount of charge in the unit as shipped from the factory.

4

Total operating charge for the condensing unit, matching indoor unit, and 25 feet

of  interconnecting pipe.

TABLE 2 - PHYSICAL DATA

Summary of Contents for E1FB180

Page 1: ...cycle plus a check valve to provide the proper flow of refrigerant through the unit during both the cooling and heating cycles All controls are located in the front of the unit and are readily access...

Page 2: ...g Operation 11 Heating Operation 12 Defrost Cycle 12 Operation Below 0 F 13 Emergency Heat Operation 13 START UP CRANKCASE HEATER 10 Ton Unit Only 14 PRE START CHECK 14 INITIAL START UP 14 SAFETY FEAT...

Page 3: ...on re quirements GROUND LEVEL LOCATIONS The units must be installed on a substantial base that will not settle Any strain on the refrigerant lines may cause a refriger ant leak Aone piece concrete sla...

Page 4: ...he dis connect switch and the unit Refer to Figure 4 for the location of the power wire access opening through the front of the unit This opening will re quire a field supplied conduit fitting The fie...

Page 5: ...1 System 2 Power Supply Power Supply Maximum Fuse Size 1 Minimum Wire Size AWG 2 Maximum Wire Length feet 3 Minimum Disconnect Amps E1FB180A25 208 230 3 60 32 1 195 0 32 1 195 0 208 230 1 60 1 4 7 1...

Page 6: ...Bottom2 0 1 Units must be installed outdoors Overhanging structures or shrubs should not obstruct condenser air discharge 2 Adequate snow clearance must be provided if winter operation is expected Co...

Page 7: ...t be designed for the pressure drop due to both friction loss and vertical rise If the total pressure drop exceeds 40 psi some refrigerant may flash before it reaches the thermal expansion valve This...

Page 8: ...left on these surfaces may lead to a future system malfunction NOTE Use only copper tubing that has been especially cleaned and dehydrated for refrigerant use If the tub ing has been open for an exte...

Page 9: ...d EXTENDING THE SERVICE PORTS Refer to Fig 5 1 Loosen the screws that secure the service ports in shipping position 2 Push the service ports through the corner post 3 Tighten the screws to secure the...

Page 10: ...or the outdoor unit the indoor unit and the refrig erant lines using information in Tables 2 Physi cal Data and 6 Refrigerant Line Charge Using the charging procedures outlined above weigh the require...

Page 11: ...diagram COOLING OPERATION 1 The following controls will be energized through terminal O on the thermostat to put the system in the cooling mode Relays RY3 RY4 RY5 and RY6 2 If the fan switch on the t...

Page 12: ...hermostat will cycle the unit to satisfy the heating re quirements of the conditioned space 5 After the unit has shutdown from a heating cycle or a power interruption the anti short cycle feature of t...

Page 13: ...the room thermostat same as described under Item 8 of HEATING OPERA TION 2 The indoor section blower operation will be controlled by the first stage heating TH1 of the room thermostat if the fan switc...

Page 14: ...Check for any abnormal noises and or vibrations and make the necessary adjustments to correct e g fan blade touching shroud refrigerant lines hitting on sheet metal etc 8 After the unit has been oper...

Page 15: ...0 Suction Pressure psig Discharge Pressure psig 115 F 105 F 95 F 85 F 75 F ODDB 150 200 250 300 350 400 450 50 60 70 80 90 Suction Pressure psig Discharge Pressure psig 115 F 105 F 95 F 85 F 75 F ODDB...

Page 16: ...180A 50 100 150 200 250 300 350 400 30 40 50 60 70 80 90 Suction Pressure psig Discharge Pressure psig 80 F 70 F 60 F IDDB FIG 10 HEATING MODE CHARGING CHART AT 6000 CFM EFB180A 50 100 150 200 250 300...

Page 17: ...B180A 50 100 150 200 250 300 350 400 30 40 50 60 70 80 90 Suction Pressure psig Discharge Pressure psig 80 F 70 F 60 F IDDB FIG 12 HEATING MODE CHARGING CHART AT 6400 CFM EFB240A 50 100 150 200 250 30...

Page 18: ...EFB240A 50 100 150 200 250 300 350 30 40 50 60 70 80 90 Suction Pressure psig Discharge Pressure psig 80 F 70 F 60 F IDDB FIG 14 HEATING MODE CHARGING CHART AT 7600 CFM EFB240A 50 100 150 200 250 300...

Page 19: ...NOTES Unitary Products Group 19 035 16192 001 A 1001...

Page 20: ...up 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright by York International Corporation 2001 All Rights Reserved Code SBY 035 16192 001 A 1001 Supersedes...

Reviews: