background image

107272-UIM-B-1105

Unitary Products Group

23

SPECIFICATIONS

Models:

Table 11 lists the major features and the applicable wiring diagram num-
bers for the R7184.

Timing:

1.

Safe Start Check: 5 seconds (approximately)

2.

Valve-on Delay: 15 seconds.

3.

Burner motor-off Delay: 0, 2, 4, or 6 minutes. Field selectable
using dual in-line programmable (DIP) switch positions 1 and 2.
Select models have 0.5, 2, 4, or 8 minute delays.

NOTE: Valve-on delay and burner motor-off delay timings can be
enabled (values as listed) or disabled (values are zero) in the field,
using DIP switch position 3.

4.

Lockout: 15, 30, or 45 seconds (factory-programmed).

5.

Recycle: 60 seconds (fixed).

6.

Ignition Carryover: 10 seconds (fixed).

Electrical Ratings:

Inputs:

a.

Voltage: 102 to 132 VAC, 120 VAC nominal.

b.

Current: 100 mA plus burner motor, valve and igniter loads.

c.

Frequency: 60 Hz.

Outputs:

a.

Burner: 120 VAC, 10 full load amperes (FLA), 60 locked rotor
amperes (LRA).

b.

Valve: 120 VAC, 1A

c.

Igniter: 120 VAC, 360 VA

d.

Alarm: 30 VAC, 2A

e.

Thermostat Current Available: 100mA

F.

EnviraCOM

TM 

Current Available: 150mA

NOTE: Reduce burner FLA rating by igniter load. For example, if the
igniter draws 3A (120 VAC, 360 VA), reduce the burner motor FLA to
7A.

SECTION VIII: START-UP AND 

ADJUSTMENTS

The initial start-up of the furnace requires the following additional
procedures:

IMPORTANT: All electrical connections made in the field and in the fac-
tory should be checked for proper tightness.

When the oil line is initially connected to the furnace, the tubing may be
full of air. In order to purge this air, it is recommended that the bleed
valve be loosened until no air bubbles are detected in the plastic tubing.
If burner does not light, press the reset button on the primary control
once only and bleed oil pump again. If burner still does not light, turn off
the power to the furnace and call a qualified service technician. DO
NOT CONTINUE TO PRESS THE RESET BUTTON ON THE PRI-
MARY CONTROL
.

TOOLS AND INFORMATION THAT WILL BE 

REQUIRED IN ORDER TO PROPERLY PERFORM THE 

FURNACE STARTUP PROCEDURE.

1.

You will need a thermometer or portable digital thermometer to
read the supply and return air temperatures. 

2.

You will need a pressure gauge that has the ability to read pres-
sures between 0 - 100 PSIG (0 - 689 kPa) in order to measure the
oil pump pressures. 

3.

You will need a 3/32” Allen wrench for the pressure port adjust-
ment screw in the oil pump. 

4.

You will need 1 piece of 1/4” (0.63 cm) ID flexible tubing that is 12”
(30 cm) in length

5.

You will need a clear plastic jug.

6.

You will need a 7/16” open end or box wrench.

7.

You will need a 1/4” brass NPT x flare fitting.

These items are required in order to properly perform the required start-
up procedure.

START-UP AND ADJUST BURNER

Start-up Burner / Set Combustion

1.

Open the shut-off valves in the oil supply line to the burner.

2.

Set the air boot adjustment to the setting stated in Table 12. This is
an initial air setting. Additional adjustments must be made with
instruments.

3.

Set the thermostat substantially above room temperature.

4.

Close the line voltage switch to start the burner. If the burner does
not start, you may have to reset the safety switch of the burner pri-
mary control.

5.

Vent air from fuel pump as soon as burner motor starts rotating.

To vent the fuel pump, attach a clear plastic hose over the vent
plug. Loosen the plug and catch the oil in an empty container.

Tighten the plug when all air has been purged from the oil supply
system.

If the burner locks out on safety during venting, quickly close the
vent plug, reset the safety switch, open the vent plug when the
motor starts rotation, and complete the venting procedure.

NOTE: Electronic safety switches can be reset immediately; others may
require a 3 to 5 minute wait.

If the burner stops after flame is established, additional venting is
probably required. Repeat the venting procedure until the pump
is primed and a flame is established when the vent plug is closed.

For R7184 primary controls, see Technician’s Quick Reference
Guide
, Beckett part number 61351, for special pump priming
sequence.

Prepare for combustion tests by taking a sample in the flue pipe.
A combustion sample should be taken with a 1/4” (0.4 km) tube
placed in the center of the vent pipe outside beneath the crown
assembly.

6.

Initial air adjustment - Using a smoke tester, adjust the air to obtain
a clean flame. Now the additional combustion tests with instru-
ments can be made. Never drill a hole in the roof jack to take com-
bustion sample or smoke tests.

TABLE 12: Burner Specifications

Furnace Model

Burner Spec

ATC

Head

Static Plate

Nozzle

Pump Pressure

Air Boot Setting

DFAA084BBTA

DFAH084BBSA

EVC - 201

AF36YHHS

F3

3 - 3/8 U

0.65 x 70° A

Delavan

100 psi (689 kPa)

4.0

DFAA066BBTA

DFAH066BBSA

EVC - 202

AF36YHHS

F3

3 - 3/8 U

0.50 x 70° A

Delavan

100 psi (689 kPa)

3.0

Do not attempt to start the burner when excess fuel or vapor has
accumulated in the appliance. Starting the burner under these con-
ditions could result in a puff back of hot combustion gases, high
smoke levels, or otherwise hazardous operation.

Summary of Contents for DFAA

Page 1: ...33 WIRING DIAGRAM GAS CONVERSION BURNER 38 LIST OF FIGURES Label Location 4 Dimensions 5 Air Distribution Systems 7 Closet To Door Clearance 5 or Greater 7 Furnace To Closet Door Clearance 1 To 5 7 Fu...

Page 2: ...rating plate and the firing input rate must be set to the unit nameplate value e The external static pressure of the air distribution system ductwork must be set for heating operation to be at least 0...

Page 3: ...solutions Chlorinated waxes and cleaners Chlorine based swimming pool chemicals Water softening chemicals De icing salts or chemicals Carbon tetrachloride Halogen type refrigerants Cleaning solvents...

Page 4: ...to the unit The following minimum clearances are recommended 1 Twenty four 24 inches 61 cm between the front of the furnace and an adjacent wall or another appliance when access is required for servic...

Page 5: ...manually operated the damper must be equipped with means to pre vent the furnace or the air conditioner from operating unless the damper is in full heat or cool position The duct system is a very imp...

Page 6: ...t design shall be in accordance with the latest HRA Digest the ASHRAE Handbook Fundamentals or other good engineering prin ciples NOTE Refer to HRA Digest Residential Air System Design Manual Sections...

Page 7: ...the front of furnace 6 inches 15 2 cm minimum clearance must be provided on side where return is located and FIGURE 5 Furnace To Closet Door Clearance 1 To 5 Furnace to Closet Door Clearance Greater...

Page 8: ...es FIGURE 7 Duct Connector Dimensions 2 3 8 6 0 cm 12 30 5 cm 13 33 0 cm 11 27 9 cm 18 3 4 47 6 cm 14 35 6 cm SEE CHART DUCT CONNECTOR PART NUMBER DUCT CONNECTOR DEPTH 7990 6011 7990 6021 7990 6041 79...

Page 9: ...terlock system usu ally contains a heat cool switch which must be turned to either HEAT or COOL to activate either heating or cooling operation or a positive OFF switch on the cooling thermostat When...

Page 10: ...er is to be placed on the top cover and secured with screws as shown in Figure 14 The power wires for the Blend Air Damper are inserted through the 7 8 2 22 cm hole in the top cover The wires to the B...

Page 11: ...ity Fuel Line Installation Continuous lengths of heavy wall copper tubing are recom mended Always use flare fittings Never use compression fit tings Always install fittings in accessible locations Fue...

Page 12: ...Fire Protection Standard for Liquid Fuel Equipment NFPA 31 or in Canada the installation must comply with CSA B139 This pump must be used with a control system that provides a valve on delay pre purge...

Page 13: ...8 SOLENOID WIRING DISCONNECT THE POWER SUPPLY BEFORE WIRING TO PRE VENT ELECTRICAL SHOCK OR EQUIPMENT DAMAGE Lead wires on these devices are long enough to reach the junction box on most burner instal...

Page 14: ...owing directly on the thermostat The wall thermostat should be located 52 to 66 inches above the floor The preferred location is on an inside wall situated in an area with good air circulation and whe...

Page 15: ...sealant or other suitable sealant INSTALLATION IN SNOW REGIONS When the combustion air pipe inlet is covered or blocked with snow the furnace will not operate properly due to the depleted combustion a...

Page 16: ...o Vent Connector and Air Intake Connector and compress gasket See Figure 29 Refer to Interior Roof Jack Extension installation instructions if applicable 4 Align holes in Roof Jack and Air Intake Conn...

Page 17: ...lk 900 sealant Not required for Roof Jacks with fixed slant flashing Complete Installation as required 1 Install Exterior Roof Jack Extension if applicable Refer to installa tion instructions provided...

Page 18: ...4084 7141 is dimensionally the same as 4000 7141 C and is available only in Canada The 4084 7151 is dimensionally the same as 4000 7151 C and is available only in Canada DFAH FURNACES DFAA FURNACES IN...

Page 19: ...0 8181 C SWIVEL FLASHING ADJUSTS FROM 0 12 TO 5 12 PITCH SLANT FLASHING 3 12 PITCH 76 59 1 2 IMPORTANT A B Warm Air Duct Duct Connector Warm Air Duct Duct Connector Floor DFAA MODELS Carefully Sealant...

Page 20: ...Cap Crown Assembly Base STEP 1 Remove upper and lower cap Remove the two 2 screws that secure the upper cap to the crown assembly base and remove the upper cap Next remove the three 3 screws that sec...

Page 21: ...in the vicinity of the vent Also in accordance with the current UL 727 Standard for safety for oil fired central furnaces FIGURE 34 Home Layout L E D B V V V X V B V J X B B B V V F V C B X V I V G H...

Page 22: ...ntrol has entered the Run mode press and release the reset button See Table 10 for equivalent cad cell resistance Preliminary Steps 1 Check wiring connections and power supply 2 Make sure power is on...

Page 23: ...ID flexible tubing that is 12 30 cm in length 5 You will need a clear plastic jug 6 You will need a 7 16 open end or box wrench 7 You will need a 1 4 brass NPT x flare fitting These items are require...

Page 24: ...fications ADJUSTMENT OF TEMPERATURE RISE After about 20 minutes of operation determine the furnace temperature rise Take readings of both the return air and the heated air in the ducts about six feet...

Page 25: ...trimmed as necessary TABLE 14 Blower Performance CFM BLOWER PERFORMANCE CFM DFAA066 FACTORY EQUIPPED WITH STANDARD BLOWERS AND FILTERS EXTERNAL STATIC PRESSURE INCHES WC kPa Blower Speed BTU H kW Inpu...

Page 26: ...Fan 15 Combustion Chamber Assembly 16 Oil Burner Assembly 17 Switch Limit Open 140 Close 110 18 Fastener Door Latch 2 Required 19 Diagram Wiring DFAH MODEL ITEM NUMBER DESCRIPTION 1 Limit Switch Manu...

Page 27: ...107272 UIM B 1105 Unitary Products Group 27 SECTION IX WIRING DIAGRAM OIL FIRED FURNACE FIGURE 37 Wiring Diagram for DFAA Oil Fired Furnace...

Page 28: ...107272 UIM B 1105 28 Unitary Products Group FIGURE 38 Wiring Diagram for DFAH Oil Furnace...

Page 29: ...ols will be readily accessible for inspection cleaning adjust ment and repairs GAS PIPING Installation and Checking of Gas Line Gas Supply piping must be sized in accordance with the recommenda tions...

Page 30: ...ape should be closed Immediately after turning on gas the system should be checked for leaks This can be done by watching the 1 2 cubic feet 0 14 m3 test dial and allowing 5 minutes to show any moveme...

Page 31: ...E EXCESSIVE PIPE SEALANT ON PIPE JOINTS Pipe sealant metal chips or other foreign material that could be deposited in the inlet of the gas valve when gas pipe is installed or carried through the gas p...

Page 32: ...1 0 147 26 9951 1471 0 154 23 9951 1541 0 173 17 9951 1731 5 000 1524 0 128 30 9951 1281 0 144 27 9951 1441 0 152 24 9951 1521 0 169 18 9951 1691 6 000 1829 0 128 30 9951 1281 0 144 27 9951 1441 0 149...

Page 33: ...monoxide poisoning or death The following steps shall be followed for each appliance connected to the venting system being placed into operation while all other appliances connected to the venting sys...

Page 34: ...3600 then divided by the time it took to measure 0 10 m3 of gas from the gas meter For Propane LP Gas multiply the Heat content of the gas MJ m3 or Default 93 15 times 0 10 m3 of gas measured at the g...

Page 35: ...ts on the gas valve marked OUT and INLET IMPORTANT The cap for the pressure regulator must be removed entirely to gain access to the adjustment screw Loosening or tightening the cap does not adjust th...

Page 36: ...has been obtained re adjust the primary air damper open or closed to visually obtain a blue flame with well defined orange or yellow tips for natural gas or well defined yellow tips for propane gas 2...

Page 37: ...ion air pres sure is sensed by the air proving switch and closes the switch contacts energizing the S89F gas primary control The S87K gas primary control has an internal 30 second prepurge timer After...

Page 38: ...107272 UIM B 1105 38 Unitary Products Group SECTION XII WIRING DIAGRAM GAS CONVERSION BURNER FIGURE 45 Wiring Diagram for DFAA Gas Conversion Burner...

Page 39: ...107272 UIM B 1105 Unitary Products Group 39 FIGURE 46 Wiring Diagram for DFAH Gas Gun...

Page 40: ...o change without notice Printed in U S A 107272 UIM B 1105 Copyright by York International Corp 2005 All rights reserved Supersedes 107272 UIM A 0905 Unitary 5005 Norman Product York OK Group Drive 73...

Reviews: