NOTICE SPECIAL REQUIREMENTS

THE EFFECT OF ELEVATION ON OIL BURNER 

FIRING

The elevation of the installation of a modern high-speed flame retention
oil burner affects the performance of the burner. Allowance for elevation
must be taken into consideration when choosing an oil burner and oper-
ating it above 2000 ft. (610m).

It is especially important in high elevation installations to adjust air set-
tings to match the burner nozzle firing rate. As elevation increases
above sea level, the ambient air contains less oxygen. Because there is
less available oxygen per cubic foot of air, the burner must deliver a
greater volume flow (cfm) of air to provide the proper amount of oxygen
for the amount of oil being burned. This is the reason that an increase in
the burner air setting may be required.

It is also important in high elevation installations to consider the maxi-
mum firing rate of the burner, so that the heat input as required by the
application is maintained. Regardless of elevation, the oil burner has a
maximum volume flow of air that it can deliver. As a result, the maxi-
mum firing rate of the oil burner decreases as the elevation increases,
because the combustion air contains less oxygen. An increase in the
size of a fixed-type retention head, or even the use of an oil burner with
a higher maximum firing rate may be necessary.

The effect of elevation up to 2000 ft. (610 m) is minimal, so no re-rate is
necessary up to 2000 ft. (610 m) elevation. Above 2000 ft. (610 m), for
every 1000 ft. (305 m) above sea level (including the first 2000 ft. (610
m), there is a 1.84% rate reduction of the burner. To assist you, we have
included the following chart and some examples: Refer to Table 7.

ft = feet
m = meters
gph = gallons per hour
l/h = liters per hour

EXAMPLE 1:

.

INSTALLATION AND CHECKING OF OIL PIPING

Location and installation of oil tanks and oil piping must comply with
local codes and regulations. In absence of such codes, follow NFPA 31:
Standard Floor Installation of Oil Burner Equipment.

This equipment must be installed, adjusted, and started only by a
qualified service technician, an individual or agency, licensed and
experienced with all codes and ordinances, who is responsible for
the installation and adjustment of the equipment. The installation
must comply with all local codes and ordinances and with the
National Fire Protection Standard for Liquid Fuel Equipment, NFPA
31 (or in Canada the installation must comply with CSA B139).

This pump must be used with a control system that provides a valve
on delay (pre-purge).

This furnace is designed to operate on #1 FUEL-OIL or #2 FUEL-
OIL ONLY. Do Not burn any other fuel in this furnace. Burning any
fuel except #1 FUEL-OIL or #2 FUEL-OIL in this furnace can cause
premature heat exchanger burnout, high levels of carbon monox-
ide, excessive sooting, a fire hazard, personal injury, property dam-
age, and/or death.
In Canada, the furnace is designed to operate on #1 STOVE OIL or
#2 FURNACE OIL ONLY.

The pressure regulator on the fuel pump must not be adjusted in
excess of 100 PSIG (689 kPa).
Pressures exceeding 100 PSIG (689 kPa) may cause an overheat-
ing condition which can lead to premature heat exchanger failure,
resulting in a fire or explosion, or cause damage to the furnace of
some of its components that will result in property damage and loss
of life. Refer to Figure 16 for Pressure Regulator Location.

TABLE 7: Burner Rating at Elevation Above Sea Level, gph (l/m)

Elevation

(Above Sea Level)

Nozzle Size

0.50

1.892706

0.65

2.460518

ft

m

gph

l/h

gph

l/h

500

152

0.50

1.89

0.65

2.46

1,000

305

0.50

1.89

0.65

2.46

1,500

457

0.50

1.89

0.65

2.46

2,000

610

0.50

1.89

0.65

2.46

2,500

762

0.49

1.86

0.65

2.46

3,000

914

0.48

1.82

0.64

2.42

3,500

1,067

0.48

1.82

0.64

2.42

4,000

1,219

0.47

1.79

0.63

2.37

4,500

1,372

0.47

1.79

0.63

2.37

5,000

1,527

0.46

1.76

0.61

2.33

5,500

1,676

0.46

1.76

0.61

2.33

6,000

1,829

0.46

1.72

0.60

2.28

6,500

1,981

0.46

1.72

0.60

2.28

7,000

2,134

0.45

1.69

0.59

2.24

7,500

2,286

0.45

1.69

0.59

2.24

8,000

2,438

0.44

1.66

0.58

2.20

9,000

2,743

0.43

1.63

0.57

2.16

10,000

3,048

0.42

1.60

0.56

2.12

Note: All examples are for 7000 ft. elevation.
1.84% x 7 (for 7000 ft.) = 12.9%   

→   

100% - 12.9% = 87.1%

Re-Rating of the Maximum Firing Rate for Burners @ 7000 ft.

Burner

Model

Maximum Firing

Rate of Burner

@ Sea Level

X

Elevation

Re-rate Factor

@ 7000 ft.

=

Adjusted

Maximum

Firing Rate

AFG

3.00 gph (11.4 L/h) X

87.1%

= 2.61 gph (9.83 Lh)

AF

3.00 gph (11.4 L/h) X

87.1%

= 2.61 gph (9.83 Lh)

 FIGURE 16:  Oil Pump

4 GPH 100-150 PSI 3450 RPM

3 GPH 150-200 PSI 3450 RPM

NO. 2 & LIGHTER FUEL

INLET

BY-PASS

Exclusively for Beckett

Made by Suntec

INLET

NO. 2 FUEL

A2EA-6520

Beckett

CLEAN

CUT

USE ONLY WITH

VALVE ON DELAY

Pressure
Adjustment
Screw

Inlet Port
1/4 NPTF

Bleed &
Gauge Port

Return Port
Install 1/16” by Pass Pipe
Plug For Two-Pipe System Only
(Use 5/32” Allen Wrench)

Cordset

By Pass
Solenoid
Valve

Inlet Port

1/4 NPTF
(0.64 cm)

Nozzle Port
3/16 Flare
Fittting

Summary of Contents for DFAA

Page 1: ...33 WIRING DIAGRAM GAS CONVERSION BURNER 38 LIST OF FIGURES Label Location 4 Dimensions 5 Air Distribution Systems 7 Closet To Door Clearance 5 or Greater 7 Furnace To Closet Door Clearance 1 To 5 7 Fu...

Page 2: ...rating plate and the firing input rate must be set to the unit nameplate value e The external static pressure of the air distribution system ductwork must be set for heating operation to be at least 0...

Page 3: ...solutions Chlorinated waxes and cleaners Chlorine based swimming pool chemicals Water softening chemicals De icing salts or chemicals Carbon tetrachloride Halogen type refrigerants Cleaning solvents...

Page 4: ...to the unit The following minimum clearances are recommended 1 Twenty four 24 inches 61 cm between the front of the furnace and an adjacent wall or another appliance when access is required for servic...

Page 5: ...manually operated the damper must be equipped with means to pre vent the furnace or the air conditioner from operating unless the damper is in full heat or cool position The duct system is a very imp...

Page 6: ...t design shall be in accordance with the latest HRA Digest the ASHRAE Handbook Fundamentals or other good engineering prin ciples NOTE Refer to HRA Digest Residential Air System Design Manual Sections...

Page 7: ...the front of furnace 6 inches 15 2 cm minimum clearance must be provided on side where return is located and FIGURE 5 Furnace To Closet Door Clearance 1 To 5 Furnace to Closet Door Clearance Greater...

Page 8: ...es FIGURE 7 Duct Connector Dimensions 2 3 8 6 0 cm 12 30 5 cm 13 33 0 cm 11 27 9 cm 18 3 4 47 6 cm 14 35 6 cm SEE CHART DUCT CONNECTOR PART NUMBER DUCT CONNECTOR DEPTH 7990 6011 7990 6021 7990 6041 79...

Page 9: ...terlock system usu ally contains a heat cool switch which must be turned to either HEAT or COOL to activate either heating or cooling operation or a positive OFF switch on the cooling thermostat When...

Page 10: ...er is to be placed on the top cover and secured with screws as shown in Figure 14 The power wires for the Blend Air Damper are inserted through the 7 8 2 22 cm hole in the top cover The wires to the B...

Page 11: ...ity Fuel Line Installation Continuous lengths of heavy wall copper tubing are recom mended Always use flare fittings Never use compression fit tings Always install fittings in accessible locations Fue...

Page 12: ...Fire Protection Standard for Liquid Fuel Equipment NFPA 31 or in Canada the installation must comply with CSA B139 This pump must be used with a control system that provides a valve on delay pre purge...

Page 13: ...8 SOLENOID WIRING DISCONNECT THE POWER SUPPLY BEFORE WIRING TO PRE VENT ELECTRICAL SHOCK OR EQUIPMENT DAMAGE Lead wires on these devices are long enough to reach the junction box on most burner instal...

Page 14: ...owing directly on the thermostat The wall thermostat should be located 52 to 66 inches above the floor The preferred location is on an inside wall situated in an area with good air circulation and whe...

Page 15: ...sealant or other suitable sealant INSTALLATION IN SNOW REGIONS When the combustion air pipe inlet is covered or blocked with snow the furnace will not operate properly due to the depleted combustion a...

Page 16: ...o Vent Connector and Air Intake Connector and compress gasket See Figure 29 Refer to Interior Roof Jack Extension installation instructions if applicable 4 Align holes in Roof Jack and Air Intake Conn...

Page 17: ...lk 900 sealant Not required for Roof Jacks with fixed slant flashing Complete Installation as required 1 Install Exterior Roof Jack Extension if applicable Refer to installa tion instructions provided...

Page 18: ...4084 7141 is dimensionally the same as 4000 7141 C and is available only in Canada The 4084 7151 is dimensionally the same as 4000 7151 C and is available only in Canada DFAH FURNACES DFAA FURNACES IN...

Page 19: ...0 8181 C SWIVEL FLASHING ADJUSTS FROM 0 12 TO 5 12 PITCH SLANT FLASHING 3 12 PITCH 76 59 1 2 IMPORTANT A B Warm Air Duct Duct Connector Warm Air Duct Duct Connector Floor DFAA MODELS Carefully Sealant...

Page 20: ...Cap Crown Assembly Base STEP 1 Remove upper and lower cap Remove the two 2 screws that secure the upper cap to the crown assembly base and remove the upper cap Next remove the three 3 screws that sec...

Page 21: ...in the vicinity of the vent Also in accordance with the current UL 727 Standard for safety for oil fired central furnaces FIGURE 34 Home Layout L E D B V V V X V B V J X B B B V V F V C B X V I V G H...

Page 22: ...ntrol has entered the Run mode press and release the reset button See Table 10 for equivalent cad cell resistance Preliminary Steps 1 Check wiring connections and power supply 2 Make sure power is on...

Page 23: ...ID flexible tubing that is 12 30 cm in length 5 You will need a clear plastic jug 6 You will need a 7 16 open end or box wrench 7 You will need a 1 4 brass NPT x flare fitting These items are require...

Page 24: ...fications ADJUSTMENT OF TEMPERATURE RISE After about 20 minutes of operation determine the furnace temperature rise Take readings of both the return air and the heated air in the ducts about six feet...

Page 25: ...trimmed as necessary TABLE 14 Blower Performance CFM BLOWER PERFORMANCE CFM DFAA066 FACTORY EQUIPPED WITH STANDARD BLOWERS AND FILTERS EXTERNAL STATIC PRESSURE INCHES WC kPa Blower Speed BTU H kW Inpu...

Page 26: ...Fan 15 Combustion Chamber Assembly 16 Oil Burner Assembly 17 Switch Limit Open 140 Close 110 18 Fastener Door Latch 2 Required 19 Diagram Wiring DFAH MODEL ITEM NUMBER DESCRIPTION 1 Limit Switch Manu...

Page 27: ...107272 UIM B 1105 Unitary Products Group 27 SECTION IX WIRING DIAGRAM OIL FIRED FURNACE FIGURE 37 Wiring Diagram for DFAA Oil Fired Furnace...

Page 28: ...107272 UIM B 1105 28 Unitary Products Group FIGURE 38 Wiring Diagram for DFAH Oil Furnace...

Page 29: ...ols will be readily accessible for inspection cleaning adjust ment and repairs GAS PIPING Installation and Checking of Gas Line Gas Supply piping must be sized in accordance with the recommenda tions...

Page 30: ...ape should be closed Immediately after turning on gas the system should be checked for leaks This can be done by watching the 1 2 cubic feet 0 14 m3 test dial and allowing 5 minutes to show any moveme...

Page 31: ...E EXCESSIVE PIPE SEALANT ON PIPE JOINTS Pipe sealant metal chips or other foreign material that could be deposited in the inlet of the gas valve when gas pipe is installed or carried through the gas p...

Page 32: ...1 0 147 26 9951 1471 0 154 23 9951 1541 0 173 17 9951 1731 5 000 1524 0 128 30 9951 1281 0 144 27 9951 1441 0 152 24 9951 1521 0 169 18 9951 1691 6 000 1829 0 128 30 9951 1281 0 144 27 9951 1441 0 149...

Page 33: ...monoxide poisoning or death The following steps shall be followed for each appliance connected to the venting system being placed into operation while all other appliances connected to the venting sys...

Page 34: ...3600 then divided by the time it took to measure 0 10 m3 of gas from the gas meter For Propane LP Gas multiply the Heat content of the gas MJ m3 or Default 93 15 times 0 10 m3 of gas measured at the g...

Page 35: ...ts on the gas valve marked OUT and INLET IMPORTANT The cap for the pressure regulator must be removed entirely to gain access to the adjustment screw Loosening or tightening the cap does not adjust th...

Page 36: ...has been obtained re adjust the primary air damper open or closed to visually obtain a blue flame with well defined orange or yellow tips for natural gas or well defined yellow tips for propane gas 2...

Page 37: ...ion air pres sure is sensed by the air proving switch and closes the switch contacts energizing the S89F gas primary control The S87K gas primary control has an internal 30 second prepurge timer After...

Page 38: ...107272 UIM B 1105 38 Unitary Products Group SECTION XII WIRING DIAGRAM GAS CONVERSION BURNER FIGURE 45 Wiring Diagram for DFAA Gas Conversion Burner...

Page 39: ...107272 UIM B 1105 Unitary Products Group 39 FIGURE 46 Wiring Diagram for DFAH Gas Gun...

Page 40: ...o change without notice Printed in U S A 107272 UIM B 1105 Copyright by York International Corp 2005 All rights reserved Supersedes 107272 UIM A 0905 Unitary 5005 Norman Product York OK Group Drive 73...

Reviews: