EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
No.
Items
Optional Function
Individual
Setting
Setting
Condition
Contents
1
b1
Cancellation of Heating
Temperature Compensation
due to Uneven Heat Load
○
00
01
02
03
04
Standard (Set Temp. +7
o
F (+4
o
C))
Removal (Set Temp.)
Set Temp. +3
o
F (+2
o
C) (*1)
Set Temp. +5
o
F (+3
o
C)
Set Temp. +2
o
F (+1
o
C)
2
b2
Circulator Function during
Heating Thermo-OFF
○
00
01
Not Available
Available
3
b3
Not Prepared
-
-
Not Used (Use as 00 conditions)
4
b4
Change of Filter Cleaning Time
-
00
01
02
03
04
Standard 1,200 hrs (Factory-Setting)
100 hrs
1,200 hrs
2,500 hrs
No Indication
5
b5
Fixing of Operation Mode
×
00
01
Standard
Fixed
6
b6
Fixing of Setting Temperature
×
00
01
Standard
Fixed
7
b7
Fixing of Operation as
Exclusive Cooling Unit
×
00
01
Standard
Fixed
8
b8
Automatic COOL/HEAT Operation
×
00
01
Not Available
Available
9
b9
Fixing of Fan Speed
×
00
01
Standard
Fixed
10
bA
Not Prepared
-
-
Not Used
11
bb
Cooling Temperature Compensation
due to Uneven Heat Load
×
00
01
02
Standard (No Compensation)
Set Temp. –2
o
F (–1
o
C)
Set Temp. –3
o
F (–2
o
C)
12
bC
Not Prepared
-
-
Not Used (Use as 00 conditions)
13
bd
Not Prepared
-
-
Not Used (Use as 00 conditions)
14
bE
Not Prepared
-
-
Not Used (Use as 00 conditions)
15
C1
Not Prepared
-
-
Not Used (Use as 00 conditions)
16
C2
Not Prepared
-
-
Not Used
17
C3
Not Prepared
-
-
Not Used
18
C4
Not Prepared
-
-
Not Used
19
C5 EconoFresh Pressure Mode (*8)
○
00
01
02
Not Available (Factory-Setting)
EconoFresh Pressure Mode
Not Available
20
C6 Hi Speed during Heating Thermo-
OFF
○
00
01
Not Available
Available
21
C7
Canceling of Enforced 3 Minutes
Minimum Operation Time of
Compressor
○
00
01
Standard
Cancellation
22
C8 Thermistor of Wired Controller (*6)
○
00
01
02
Not Available
Control by Thermistor of Wired Controller
Control by Average Value of Indoor Air Inlet
Thermistor and Thermistor of Wired Controller
23
C9
Not Prepared
-
-
Not Used
24
CA
Not Prepared
-
-
Not Used
25
Cb Selection of Forced Stoppage Logic
×
00
01
Forced Stoppage Input: A Contact
Forced Stoppage Input: B Contact
26
CC
Not Prepared
-
-
Not Used (Use as 00 conditions)
● for Ducted (Medium Static) with EconoFresh Kit
5.4.2.1 Function Selection Item
5.4.2 Function Setting
Summary of Contents for CIDM030B21E
Page 2: ......
Page 10: ...viii SM 16005 rev 2...
Page 14: ......
Page 15: ...SM 16005 rev 2 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 16005 rev 2 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 16005 rev 2 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 70: ......
Page 71: ...SM 16005 rev 2 4 1 MAINTENANCE 4 Maintenance...
Page 130: ......
Page 131: ...SM 16005 rev 2 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 140: ...6 10 SM 16005 rev 2 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 141: ...SERVICE PARTS LIST SM 16005 rev 2 7 1 7 Service Parts List...
Page 143: ......
Page 144: ...2016 Johnson Controls Inc SM 16005 rev 2 Code No LIT 12012293 Revised February 2019...