SM-16005-rev.2
5-41
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
5.5.4 Comfort Function
Following functions are not available depending on connected outdoor unit.
(1) Quick Function
Do not use the Quick Function when using the Ducted (EconoFresh). When it is used, the thermal
load of heat source in the room may significantly increase depending on the outdoor temperature
conditions. Configure according to the outdoor temperature condition.
(2) Power Up Setting
If the cooling/heating capacity seems insufficient during the normal operation, set this function.
By setting this function, the target frequency and upper limit of the compressor are set higher as
follows.
Setting Condition
Power Up Mode
Compressor Frequency for Cooling Operation Compressor Frequency for Heating Operation
Upper Limit
Target Frequency
Upper Limit
Target Frequency
0 (Default Setting)
-
-
-
-
1
Default S20% Default S20%
-
-
2
-
-
Default S20% Default S20%
3
Default S20% Default S20% Default S20% Default S20%
NOTE:
The upper limit and target frequency of the compressor are same as Function Setting “Hc” or “Hh”.
Summary of Contents for CIDM030B21E
Page 2: ......
Page 10: ...viii SM 16005 rev 2...
Page 14: ......
Page 15: ...SM 16005 rev 2 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 16005 rev 2 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 16005 rev 2 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 70: ......
Page 71: ...SM 16005 rev 2 4 1 MAINTENANCE 4 Maintenance...
Page 130: ......
Page 131: ...SM 16005 rev 2 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 140: ...6 10 SM 16005 rev 2 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 141: ...SERVICE PARTS LIST SM 16005 rev 2 7 1 7 Service Parts List...
Page 143: ......
Page 144: ...2016 Johnson Controls Inc SM 16005 rev 2 Code No LIT 12012293 Revised February 2019...