SM-16005-rev.2
5-27
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(35) Not Prepared (d6)
(36) Damper Minimum Opening (d7)
This function is used to set the fresh outdoor air damper minimum opening selection.
(37) All Fresh Operation (E1)
This function allows to the outdoor air damper to be opened.
(32) Power Supply ON/OFF 2 (Restarting Function After Power Failure) (d3)
This function is utilized to restart the unit operation automatically when the power supply is restored
after a power failure of over 2 seconds. In case of power failure for 2 seconds or less, the standard
unit retains all the operational functions and restarts the operation automatically. (The compressor
restarts operation after 3 minutes guard in addition to power failure time for up to 2 seconds.)
When this function is utilized in the condition that there is no person to operate the unit, monitor the
system for potential unit failure.
NOTES:
1. If power failure occurs during the stoppage of the unit, the unit remains stopped after the power
supply is restored.
2. When the compressor does not reach the fixed temperature, the system may not restart
automatically after turning on the power supply by hot-start control.
*Hot-start Control: The control program that does not operate the compressor even after the
power is turned ON if the compressor does not reach the fixed temperature.
(33) Prevention for Cooling Discharge Air Temperature Decrease (d4)
This function is utilized to prevent discharge air temperature decrease during the cooling operation by
controlling Thermo-ON/OFF according to the discharge air temperature.
● Thermo-ON:
COOL/DRY operations continue for 3 minutes when discharge air temperature at 52
o
F (11
o
C) or lower.
● Thermo-OFF:
The room temperature reaches the setting temperature when discharge air temperature at 56
o
F (13
o
C)
or higher.
(34) Prevention for Heating Discharge Air Temperature Decrease (d5)
This function is utilized to prevent discharge air temperature decrease during the heating operation by
making the actual fan speed lower than the speed indicated on the wired controller.
NOTE:
The above table shows when the optional function setting “Hi Speed” is set as standard (00) by the
wired controller.
Large
Fan Speed
Small
Indications on
Wired Controller
HIGH2
HIGH
MED
LOW
Actual Fan Speed
HIGH
HIGH
LOW
LOW
Summary of Contents for CIDM030B21E
Page 2: ......
Page 10: ...viii SM 16005 rev 2...
Page 14: ......
Page 15: ...SM 16005 rev 2 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 16005 rev 2 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 16005 rev 2 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 70: ......
Page 71: ...SM 16005 rev 2 4 1 MAINTENANCE 4 Maintenance...
Page 130: ......
Page 131: ...SM 16005 rev 2 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 140: ...6 10 SM 16005 rev 2 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 141: ...SERVICE PARTS LIST SM 16005 rev 2 7 1 7 Service Parts List...
Page 143: ......
Page 144: ...2016 Johnson Controls Inc SM 16005 rev 2 Code No LIT 12012293 Revised February 2019...