SM-16005-rev.2
4-9
MAINTENANCE
TURN OFF all POWER supply switches.
4.2.5 Removing Electronic Expansion Valve Coil
(1) Remove the electrical box cover according to Section 4.2.1 “Removing PCB”.
(2) Disconnect the connector for the expansion valve coil located on the PCB1. Then remove the wiring.
(3) Pull the service cover slightly forward according to Section 4.2.3 “Removing Condensate Pump”.
(4) Remove the detents of the expansion valve coil from the projection parts of the valve body by rotating
the valve coil. Pull up the valve coil and remove it. At this time, take care not to twist the pipes.
(5) Insert the new expansion valve coil into the expansion valve body. When inserting the valve coil,
secure the projection parts into the detents.
NOTE:
The detents are located 90
o
apart in a circle and the projections are located 180
o
apart in a circle.
Make sure to fit the projection parts into the detents. The rotation direction does not affect the
operation. If the valve coil is inserted incorrectly, it may cause malfunction of the valve coil.
(6) When the replacement is completed, secure the wire for the expansion valve coil near the valve coil
with a plastic band. At this time, secure the edge of lead wires for the expansion valve coil to face
down.
Phillips Screwdriver
Tool
Projection
Detent
Expansion Valve Body
Expansion Valve Coil
Summary of Contents for CIDM030B21E
Page 2: ......
Page 10: ...viii SM 16005 rev 2...
Page 14: ......
Page 15: ...SM 16005 rev 2 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 16005 rev 2 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 16005 rev 2 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 70: ......
Page 71: ...SM 16005 rev 2 4 1 MAINTENANCE 4 Maintenance...
Page 130: ......
Page 131: ...SM 16005 rev 2 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 140: ...6 10 SM 16005 rev 2 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 141: ...SERVICE PARTS LIST SM 16005 rev 2 7 1 7 Service Parts List...
Page 143: ......
Page 144: ...2016 Johnson Controls Inc SM 16005 rev 2 Code No LIT 12012293 Revised February 2019...