3-4
SM-16005-rev.2
TROUBLESHOOTING
Table 3.1 Recommended Wiring Capacity and Size
Model
Power
Supply
Minimum Wire Thickness
[AWG (mm
2
)]
GFCI
<Ground Fault Circuit
Interrupter>
Main Switch
MCA
(Minimum
Circuit
Ampacity)
Power
Supply
Wiring
Size
< Main >
Ground
Wiring
Size
Comm.
Cable
Size
Nominal
Current
Nominal
Sensitive
Current
Nominal
Current
Fuse
[A]
[mA]
[A]
[A]
[A]
(H,Y,C)IDM030B21E
1~,
208/230V
60Hz
18 (0.82) 18 (0.82) 18 (0.82)
15
30
15
15
1.7
(H,Y,C)IDM036B21E
2.2
(H,Y,C)IDM048B21E
2.3
NOTES:
1) Follow local codes and regulations when selecting field wires.
2) This equipment can be installed with a Ground Fault Circuit Interrupter (GFCI), which is a recognized measure for
added protection to a properly grounded unit. Install appropriate sized breakers / fuses / overcurrent protection
switches, and wiring in accordance with local, state and NEC codes and requirements. The equipment installer is
responsible for understanding and abiding by applicable codes and requirements.
3) Total operating current should be less than 12A.
4) Fuse should be slow blowing capability.
▪ Ducted (Medium Static) with EconoFresh Kit
● This equipment can be installed with a Ground Fault Circuit Interrupter (GFCI), which is a recognized
measure for added protection to a properly grounded unit. Install appropriate sized breakers/ fuses/
overcurrent protection switches, and wiring in accordance with local, state and NEC codes and
requirements. The equipment installer is responsible for understanding and abiding by applicable codes
and requirements. Check the recommended size of ELB shown in Table 3.1.
Select high-sensitive high speed ELB or GFCI when the rated sensitive current is less than 30mA. (The
motion time should be within 0.1 second.)
● Between indoor and outdoor units, use dual-conductor,
AWG18 (0.82mm
2
) stranded copper cable for
communication cable. Do not use any cable with more than two conductors. Twisted pair or shielded cable
can be used in environments with excessive electrical noise to reduce the possibility of communication
errors between system components. Total cable length should not exceed 3281 ft (1000m).
● Select the wiring size, GFCI (Ground Fault Circuit Interrupter) in accordance with the regulations for each
region, the “Installation and Maintenance Manual”, and the dedicated electrical circuit that must be used.
● Outside of the indoor unit, installation of the power supply wiring, communication cable, and wired
controller cable should be spaced as far apart as possible.
NOTICE
Summary of Contents for CIDM030B21E
Page 2: ......
Page 10: ...viii SM 16005 rev 2...
Page 14: ......
Page 15: ...SM 16005 rev 2 1 1 INSTALLATION 1 Installation...
Page 19: ...SM 16005 rev 2 2 1 OPERATION 2 Operation...
Page 22: ......
Page 23: ...SM 16005 rev 2 3 1 TROUBLESHOOTING 3 Troubleshooting...
Page 70: ......
Page 71: ...SM 16005 rev 2 4 1 MAINTENANCE 4 Maintenance...
Page 130: ......
Page 131: ...SM 16005 rev 2 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Page 140: ...6 10 SM 16005 rev 2 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Page 141: ...SERVICE PARTS LIST SM 16005 rev 2 7 1 7 Service Parts List...
Page 143: ......
Page 144: ...2016 Johnson Controls Inc SM 16005 rev 2 Code No LIT 12012293 Revised February 2019...