PG-D2 (For V/f with PG Feedback Mode Only)
PG-D2 (For V/f with PG Feedback Mode Only)
Three-phase 200 VAC
(400 VAC)
Yd5000
Power supply +12 V
Power supply 0 V
Power supply +5 V
Pulse input + (A/B phase)
Pulse input − (A/B phase)
Pulse monitor output
Shielded twisted-pair wires must be used for signal lines.
Do not use the pulse generator’s power supply for anything other than the pulse
generator (encoder).
Using it for another purpose can cause malfunctions due
to noise.
The length of the pulse generator’s wiring must not be more than 100 meters.
PG-D2 Wiring
PG-D2 Wiring
PG-X2 (For Flux Vector Control Mode Only)
PG-X2 (For Flux Vector Control Mode Only)
Three-phase 200 VAC
(400 VAC)
Yd5000
Shielded, twisted-pair wire must be used for signal lines.
Do not use the pulse generator’s power supply for anything other than the
pulse generator (encoder)
. Using it for another purpose can cause
malfunctions due to noise.
The length of the pulse generator’s wiring must not be more than 100 meters.
The direction of rotation of the PC can be set in user constant F1-05. The
factory preset if for forward
rotation, A-phase advancement.
PG-X2 Wiring