Yokogawa Electric Corporation - TC10-L - ENGINEERING MANUAL - PAG. 15
Out 2
Function: Limiter output
Available: Ever
Output action: Reverse
Output type: relay
Contatto: SPST (NO contact)
Contact rating: - 2A / 250 V c.a. on resistive load.
1 A / 250 V with cosf = 0.4
Out 3
Function: Alarm output
Available: optionally
type : relay o SSR
a) Relay output
Contact type: SPST (No contact)
Contact rating: - 2A / 250 V c.a. on resistive load.
-1 A / 250 V with cosf = 0.4
b) Logic voltage for SSR drive.
Isolation: Output NOT isolated.
Protection: Output protected from short circuit.
1 logic status: 12 V ±20% @ 15 mA.
0 logic status: <0.5 V
Out 4 (when programmed)
Function: alarm output
Available: ever
Type : SSR drive
Isolation: Not isolated
Protection : Output protected from short circuit.
Stato logico 1: 12 V ±20% @ 23 mA.
Stato logico 0: <0.5 V
Auxiliary power supply for TX
NOTE: this output is obtained by forcing the out 4 to ON.
Isolation: Not isolated
Protection : Output protected from short circuit.
Voltage: 12 VDC
Current: 23 mA Max.
Serial interfaces
Type: TTL
Available: ever
Isolation: Not isolated
Protocol: Modbus RTU
Baud rate: from 1200 to 38400 baud
Multiple reading: max 16 word.
Multiple writing: max 16 word.
Parity: none
Data format: 8 bit
Start Bit : 1
Stop Bit: 1
Type: RS 485 optionally
Available: on request
Isolation: Isolated (50 V)
Protocol: Modbus RTU
Baud rate: from 1200 to 38400 baud
Multiple reading: max 16 word.
Multiple writing: max 16 word.
Parity: none
Data format: 8 bit
Start Bit : 1
Stop Bit: 1