an overrange error.

2. 

It is possible to set a full scale read-out lower 
than the initial scale read-out in order to obtain a 
reverse read-out scaling.

E.g.:

0 mA = 0 mBar and 20 mA = -1000 mBar (vacuum).

[5] unit - Engineering unit

Available: 

When a temperature sensor is selected by [1] 
SenS parameter.

Range: 

°C = Celsius;
°F = Fahrenheit.

[6] FiL - Digital fi lter on the measured value

Available: 

Always.

Range: 

oFF (No fi lter);
0.1 to 20.0 s.

Note: 

This is a fi rst order digital fi lter applied on the 
measured value.  For this reason it will affect the 
measured value but also the control action and the  
alarms behaviour.

[7] bS 

- PV input bias

Available: 

Always.

Range: 

In Engineering unit, it is programmable from -100 to 

100 % of the input span 

[8] di.A - Digital Input Action

Available: 

Always.

Range: 

0 = 

DI1 Direct action, 

1 = 

DI1 Reverse action, 

]

out Group - Output parameters

[9] o1.t - Out 1 type

Available: 

When the out 1 is a linear output.

Range: 

 0.20 

0 to 20 mA;

4.20 

4 to 20 mA;

0.10 

0 to 10 V;

2.10 

2 to 10 V.

[10] o1F - Out 1 function

Available: 

Always.

Range:  • 

When the out 1 is a linear output:

nonE =  Output not used.  With this setting the status 

of this output  can be driven directly from 
serial link;

r.inP =  Measured value Analog retransmission.
r.Err =  Analog retransmission of the measured 

error (PV-SP);

r.SP =  Analog retransmission of the operative set 

point;

r.SEr =  Analog retransmission of a value coming 

from serial link;

[11] Ao1L - Initial scale value of the analog 

retransmission

Available: 

When Out 1 is a present

Range: 

-1999 to [12] Ao1H.

[12] Ao1H - Full scale value of the analog 

retransmission

Available: 

When Out 1 is present

Range: 

[11] Ao1L to 9999.

[13] o3F - Out 3 function

Available: 

When the instrument has out 3 option.

Range: 

nonE =  Output not used. With this setting the status 

of the this output  can be driven directly 
from serial link;

AL =  

Alarm output;

or.bo =  Out-of-range or burn out indicator;
P.FAL =  Power failure indicator;
bo.PF =  Out-of-range, burn out and Power failure 

indicator;

[14] o3AL - Alarms linked up with Out 3

Available: 

When  [13] o3F = AL.

Range: 

0 to 15 with the following rule:
+1 = 

Alarm 1;

+2 = 

Alarm 2;

+4 = 

Sensor break (burn out);

+8 = 

Overload on Out 4 (short circuit on out 4);

[15] o3Ac - Out 3 action

Available: 

when [13] o3F is different from “nonE”.

Range: 

dir = 

Direct action;

rEU = 

Reverse action;

Notes:  1. 

Direct action: the output repeats the status of the 
driven element. Example: the output is an alarm 
output with direct action. When the alarm is ON, 
the relay will be energized (logic output 1). 

2. 

Reverse action: the output status is the opposite 
of the status of the driven element. Example: 
the output is an alarm output with reverse 
action. When the alarm is OFF, the relay will be 
energized (logic output 1). This setting is usually 
named “fail-safe” and it is generally used in 
dangerous process in order to generate an alarm 
when the instrument power supply goes OFF or 
the internal watchdog starts.

[16] o4F - Out 4 function

Available: 

Always

Range: 

nonE =  Output not used. With this setting the status 

of the this output  can be driven directly 
from serial link.

AL = 

Alarm output;

or.bo =  Out-of-range or burn out indicator;
P.FAL =  Power failure indicator;
bo.PF =  Out-of-range, burn out and Power failure 

indicator;

On = 

Output ever ON (it is used as auxiliary 
power supply for TX).

[17] o4AL - Alarms linked up with Out 4

Available: 

When  [16] o4F = AL.

Range: 

0 to 7 with the following rule.
+1 = 

Alarm 1;

+2 = 

Alarm 2;

+4 = 

Sensor break (burn out);

[18] o4Ac - Out 4 action

Available: 

When [16] o4F is different from “nonE”.

Range: 

dir = 

Direct action;

rEU = 

Reverse action;.

Summary of Contents for TC 10-L

Page 1: ...ust be mounted This is mandatory for FM approval 2 CONNECTION DIAGRAM RS485 TERMINALS Pin connector 1 4 mm max 0 055 in Stripped wire L 5 5 mm 0 21 in L ELECTRICAL CONNECTIONS Thermo couple DI1 OP3 Li...

Page 2: ...20 mA input wiring for passive transmitter using an external pws _ _ 1 2 0 4 to 20 mA Passive transmitter _ External PWS 0 4 to 20 mA input wiring for active transmitter 0 4 to 20 mA Active transmitte...

Page 3: ...5 VDC Logic level 1 12 V 20 20 mA max Note Overload protected 2 4 SERIAL INTERFACE D D D D D D D D RS 485 5 6 Interface type Isolated 50 V RS 485 Voltage levels According to EIA standard Protocol type...

Page 4: ...Resolution 30000 counts Total Accuracy 0 5 F S V 1 digit 25 C of room temperature Electromagnetic compatibility and safety requirements Compliance directive EMC 2004 108 CE EN 61326 1 directive LV 200...

Page 5: ...exceed SP at power on SP HYS PV A B D C EXCEEDED LAMP OUT LAMP lit off OUTPUT RELAY confirmation accepted lit off Energized De energized OFF OFF OFF Lit ON OFF Lit OFF Power ON OFF OFF ON OFF 5 3 HOW...

Page 6: ...TC J 50 1000 C 58 1832 F crAL TC K 50 1370 C 58 2498 F S TC S 50 1760 C 58 3200 F r TC R 50 1760 C 58 3200 F t TC T 70 400 C 94 752 F n TC N 50 1300 C 58 2372 F Pt1 RTD Pt 100 200 850 C 328 1562 F Pt1...

Page 7: ...9 13 o3F Out 3 function Available When the instrument has out 3 option Range nonE Output not used With this setting the status of the this output can be driven directly from serial link AL Alarm outpu...

Page 8: ...1 0 ON off off AL1 off off off AL1 ON ON ON ON 3 The instrument does not store in EEPROM the alarm status For this reason the alarm status will be lost if a power down occurs 21 AL1L For High and low...

Page 9: ...SE br Range 1 to 9999 engineering units Note For other details see 24 HAL1 parameter 32 AL2d Alarm 2 delay Available When 26 AL2t type is different form nonE Range From oFF 0 to 9999 seconds Note The...

Page 10: ...ilable always but it is a read only parameter Range from 00 00 to 99 59 HH mm 42 Hi maximum measured value Available Available when 33 Hi Lo Hi high limit but it is a read only parameter Range Enginee...

Page 11: ...a set point equal to the minimum value of the operative range e g 10 C When the temperature in the chamber is steady take note of the temperature measured by the reference system e g 9 C 3 Set 50 A L...

Page 12: ...Exceeded indication EX OUT PK HI AL1 AL2 TC10 L Output b c d e The HI lamp d is ON When a measured value a is higher then the set point b EX lamp e lights OUT lamp b turns ON and the limit output rel...

Page 13: ...onds 2 The upper display will show PASS while the lower display will show 0 3 By and buttons set the value assigned to 44 PAS2 Level 2 password Notes 1 The factory default password for configuration p...

Page 14: ...n EN584 1 DIN 43710 1977 TC Type Ranges J 50 to 1000 C 50 0 to 999 9 C 58 to 1832 F 58 0 to 999 9 F K 50 to 1370 C 50 0 to 999 9 C 58 to 2498 F 58 0 to 999 9 F S 50 to 1760 C 50 0 to 999 9 C 58 to 320...

Page 15: ...arm output Available ever Type SSR drive Isolation Not isolated Protection Output protected from short circuit Stato logico 1 12 V 20 23 mA Stato logico 0 0 5 V Auxiliary power supply for TX NOTE this...

Page 16: ...ufacturing defects or faulty materials that are found within 18 months from manufacturing date The warranty is limited to the replacement of the instrument The tampering of the instrument or an improp...

Page 17: ...ms behaviour 0 oFF to 20 0 s 1 7 bS PV input bias 100 to 100 of the input span dP 8 di A Digital Input action 0 DI1 direct 1 DI1 reverse OUT group N Param Description Range value or selection list ele...

Page 18: ...Group N Param Description Range value or selection list elements Decimal gure 26 AL2t Alarm 2 type nonE Alarm not used LoAb Absolute low alarm HiAb Absolute high alarm LHAo Absolute band alarm with a...

Page 19: ...tion Range value or selection list elements Decimal gure 44 PAS2 Password level 2 0 oFF to 200 0 45 PAS3 Password level 3 3 to 200 0 46 di CL Display color 0 The display color is used to show the Exce...

Page 20: ...Yokogawa Electric Corporation TC10 L ENGINEERING MANUAL PAG 20...

Reviews: