Yokogawa Electric Corporation - TC10 -L - ENGINEERING MANUAL - PAG. 17
Appendix A
InP Group
N
Param.
Description
Range value or selection list elements
Dec.
point
1
SEnS
Measuring input
J = TC J
crAL = TC K,
S = TC S,
r = TC R
t = TC T,
n = TC N
Pt1 = PT 100,
Pt10 = PT 1000,
0.60 = 0 to 60 mV,
12.60 = 12 to 60 mV,
0.20 = 0 to 20 mA,
4.20 = 4 to 20 mA,
0.5 = 0 to 5 V,
1.5 = 1 to 5 V,
0.10= 0 to 10 V
2.10 = 2 to 10 V,
dP
2
dP
Decimal point figure
Note: For TC and RTD inputs the decimal figure must be 0 or 1 only.
0 to 3
dP
3
SSc
Initial scale readout
NOTE: This parameter will be shown only when a linear input has been selected (mV, V or mA).
-1999 to 9999
dP
4
FSc
Full scale readout
NOTE: This parameter will be shown only when a linear input has been selected (mV, V or mA).
-1999 to 9999 (E.U.)
dP
5
unit
Engineering unit
NOTE: This parameter will be shown only when a TC or RTD input has been selected.
°C or °F
6
FiL
Digital filter on the measured value.
Note: This filter will affect the measured value but also the control action the analogue retransmis-
sion and the alarms behaviour.
0( oFF) to 20.0 (s)
1
7
bS
PV input bias
-100 to 100 % of the input span
dP
8
di.A
Digital Input action
0 = DI1 direct
1 = DI1 reverse
OUT group
N
Param.
Description
Range value or selection list elements
Decimal
point
9
O1.t
Out 1 type
NOTE: this parameter will be shown only when Out 1 is present
0.20 = 0 to 20 mA
4.20 = 4 to 20 mA
0.10 = 0 to 10 Volt
2.10 = 2 to 10 Volt
0
10
o1F
Out 1 function
nonE = Out not used
r.inP = Measure retransmission
r.Err = Error retransmission
r.SP = SP retransmission
r.SEr = Retransmission of a value coming from serial link
11
Ao1L
Retransmission – initial scale value
-1999 to Ao1H
dP
12
Ao1H
Retransmission – full scale value
Ao1L to 9999
dP
13
o3F
Out 3 function
Available: when Out 3 is present.
nonE = Out not used
AL = Alarm output
or.bo = Over-range and burn-out
P.FAL = Power failure
bo.PF = Over-range, Burn-out and power Fail
14
o3AL
Alarms linked up with Out 3
from 0 to 15
+1 = Alarm 1
+2 = Alarm 2
+4 = Burn-out
+8 = Overload of the Out 4
0
15
o3Ac
Out 3 action
dir = Direct action
rEU = Reverse action
16
o4F
Out 4 function
nonE = Out not used
AL = Alarm output
or.bo = Over-range and burn-out
P.FAL = Power failure
bo.PF = Over-range, Burn-out and power Fail
On = Output ever ON (usable as auxiliary PWS for a transmitter).