Yokogawa Electric Corporation - TC10-L - ENGINEERING MANUAL - PAG. 4
3. TECHNICAL CHARACTERISTICS
3.1 TECHNICAL SPECIFICATION
Case:
Plastic, self-extinguishing degree: V-0 according to UL 94;
Front protection:
IP 65 (when the optional panel gasket is
mounted) for indoor locations according to EN 60070-1;
Terminals protection:
IP 20 according to EN 60070-1;
Installation:
Panel mounting;
Terminal block:
16 screw terminals for cables of
0.25 to 2.5 mm
2
(AWG22 to AWG14) with connection diagram,
tightening torque 0.5 Nm;
Dimensions:
48 x 48, depth 73 mm, (1.89 x 1.89 x 2.87 in.)
Panel cutout:
45
[-0, +0.6]
x 45
[-0, +0.6]
mm
(1.78
[- 0.000, +0.023]
x 1.78
[- 0.000, +0.023]
in.)
Weight:
180 g max..
Power supply:
100 to 240 VAC (-15 to +10% of the
nominal value);
Power consumption:
6.0 VA max. (100 to 240 VAC);
Insulation voltage:
2300 V rms according to EN 61010-1;
Display updating time:
500 ms;
Sampling time:
130 ms;
Resolution:
30000 counts;
Total Accuracy:
±0.5% F.S.V. ±1 digit @ 25°C of room
temperature;
Electromagnetic compatibility and safety requirements
Compliance:
directive EMC 2004/108/CE (EN 61326-1),
directive LV 2006/95/CE (EN 61010-1),
UL 61010-1 CSA 61010-1;
Note:
During the test, the instrument continues to operate at
the measurement accuracy within specifi cation.
Installation category:
II;
Pollution category:
2;
Temperature drift:
It is part of the global accuracy;
Operating temperature:
0 to 50°C (32 to 122°F);
Storage temperature:
-20 to +70°C (-4 to +158°F);
Humidity:
20 to 95% RH, not condensing.
4. MODEL AND SUFFIX CODES
Model Code
Suffix codes
Description
TC10
-L
o
C
o o o
D
o
F
Temperature Controller
Fixed code -L
Always "-L"
Power supply
H
100 to 240 VAC
Fixed code
C
Always "C"
Retransmission
N
None
A
PV retrans. output 4 to 20 mA
Limit control output
R
limit control relay output
Alarm output 1 - 2
N
None
R
Alarm output:2 Points (OT3 relay
+ OT4 SSR drive)
Fixed code
D
Always "D"
Serial communication
S
RS485 Modbus
N
None
Fixed code
F
Always “F”
Option Code
/GK Panel gasket for IP65