6.  OPERATIVE MODES

The TC10-L is an FM (both FM3545 and FM3810) approved 
limit controller that can be confi gured either as a high limit or 
as a low limit controller by a user. 
The relay of the output 2 operates in fail-safe mode (relay 
de-energized during shutdown condition) and latching mode.
OUT 2 turns OFF (in this document this condition will be 
named shutdown) when:
The instrument is confi gured as a high limiter (Hi.Lo = Hi) 
and the measured value is greater than limiter threshold 
[“SP” parameter] or.
The instrument is confi gured as a low limiter (Hi.Lo = Lo) 
and the measured value is lower than limiter threshold. 
Out 2 remains OFF until the condition which generated the 
shutdown, no longer exists and the Confi rming action (re-
arm) has been performed.
During a shutdown (Out 2 is OFF) the upper display will be 
red.
Confi rming action (rearm) can be performed in two different 
way:
- by pressing the 

  key [when “diS” parameter is set to 

“but”] but it will be accepted only when the condition which 
generated the shutdown, no longer exists (EX lamp is OFF) 
and the set point is shown on the lower display (see “normal 
display” in “Navigation access”) 
- by momentarily closing the digital input (by an external dry 
contact) [when diS parameter is set to “di”] but it will be ac-
cepted only when the condition which generated the shut-
down, no longer exists.
We defi ne also that the time duration of the shutdown condi-
tion, stored by the instrument, will be the time from Out 2 
goes OFF (shutdown start) and the condition that generate 
the shutdown no longer exists.
The confi rmation action is not part of this time count. 
The time duration of the shutdown condition and max/min 
measured values are stored in memory and available for 
viewing (see “navigation access”) until the next shutdown 
condition occurs.
These informations are lost at power down.

6.1  HIGH LIMIT CONTROL

PV

SP

Process Value

(in eng. units)

Set Point

(a)

(Editing mode)

Limit
Control

High
Limiter

Exceeded
indication

EX

OUT

PK

HI

AL1

AL2

TC10-L

Output

(b)

(c)

(d)

(e)

The HI lamp (d) is ON
When a measured value (a) is higher then the set point 
(b),“EX” lamp (e) lights, “OUT” lamp (b) turns ON and the 
limit output relay (Out 2) is de-energized.
EX lamp (e) turns off when PV goes into normal condition, 
while the ”OUT” lamp (c) stays on as it is. 
The out (c) lamp turns off only when the EX lamp (e) is off 
and a confi rming operation (rearm) has been done by an 
operator. 
The way to confi rm are (according to the “diS” parameter):
- pressing  

  key for more than 3 seconds or 

- by DI1.
Output relay is de-energized whenever “OUT” lamp is on.
Check the “HYS” parameter value if the EX lamp (e) is not 
turn off when PV (a) is lower than SP (b).

SP

HYS

PV

(A)

(B)

(C)

(A)

(B)

(D)

EXCEEDED

LAMP

OUT

LAMP

lit

off

OUTPUT

RELAY

confirmation

(accepted)

confirmation

(not accepted)

lit

off

Energized

De-energized

OFF

OFF

OFF

Lit

Lit

OFF

Lit

ON

OFF

ON

OFF

Lit

OFF

When the EX lamp (e) is ON but PV (a) is lower than SP (b), 
the upper display will be in green color and it shows that the 
PV is in the hysteresis area

6.2  LOW LIMIT CONTROL

The HI lamp (d) is OFF
When a measured value (a) is lower than the set point (b), 
“EX” lamp (e) lights, and “OUT” lamp (c) turns ON and the 
limit output relay is de-energized. 
“EX” (e) lamp turns off when PV goes into normal condition, 
while the “OUT” lamp (c) lamp stays on as it is. 
The out (c) lamp turns off only when the EX lamp (e) is off 
and a confi rming operation (rearm) has been done by an 
operator. 
The way to confi rm are (according to the “dis” parameter):
- pressing  

  key for more than 3 seconds or 

- by DI1.
The confi rming operation is not accepted during PV exceeds 
SP (D) (during EXCEEDED lamp lights*). State of output 
relay is de-energized whenever “OUT” lamp is on.
Output relay is de-energized whenever “OUT” lamp is on.
Check the “HYS” parameter value if the EX lamp (e) is not 
turn off when PV (a) is lower than SP (b).

SP

HYS

PV

(A)

(B)

(C)

(A)

(B)

(D)

EXCEEDED

LAMP

OUT

LAMP

lit

off

OUTPUT

RELAY

confirmation

(accepted)

confirmation

(not accepted)

lit

off

Energized

De-energized

OFF

OFF

OFF

Lit

Lit

OFF

Lit

ON

OFF

ON

OFF

Lit

OFF

When the EX lamp (e) is ON but PV (a) is higher than SP 
(b), the upper display will be in green color and it shows that 
the PV is in the hysteresis area

Summary of Contents for TC 10-L

Page 1: ...ust be mounted This is mandatory for FM approval 2 CONNECTION DIAGRAM RS485 TERMINALS Pin connector 1 4 mm max 0 055 in Stripped wire L 5 5 mm 0 21 in L ELECTRICAL CONNECTIONS Thermo couple DI1 OP3 Li...

Page 2: ...20 mA input wiring for passive transmitter using an external pws _ _ 1 2 0 4 to 20 mA Passive transmitter _ External PWS 0 4 to 20 mA input wiring for active transmitter 0 4 to 20 mA Active transmitte...

Page 3: ...5 VDC Logic level 1 12 V 20 20 mA max Note Overload protected 2 4 SERIAL INTERFACE D D D D D D D D RS 485 5 6 Interface type Isolated 50 V RS 485 Voltage levels According to EIA standard Protocol type...

Page 4: ...Resolution 30000 counts Total Accuracy 0 5 F S V 1 digit 25 C of room temperature Electromagnetic compatibility and safety requirements Compliance directive EMC 2004 108 CE EN 61326 1 directive LV 200...

Page 5: ...exceed SP at power on SP HYS PV A B D C EXCEEDED LAMP OUT LAMP lit off OUTPUT RELAY confirmation accepted lit off Energized De energized OFF OFF OFF Lit ON OFF Lit OFF Power ON OFF OFF ON OFF 5 3 HOW...

Page 6: ...TC J 50 1000 C 58 1832 F crAL TC K 50 1370 C 58 2498 F S TC S 50 1760 C 58 3200 F r TC R 50 1760 C 58 3200 F t TC T 70 400 C 94 752 F n TC N 50 1300 C 58 2372 F Pt1 RTD Pt 100 200 850 C 328 1562 F Pt1...

Page 7: ...9 13 o3F Out 3 function Available When the instrument has out 3 option Range nonE Output not used With this setting the status of the this output can be driven directly from serial link AL Alarm outpu...

Page 8: ...1 0 ON off off AL1 off off off AL1 ON ON ON ON 3 The instrument does not store in EEPROM the alarm status For this reason the alarm status will be lost if a power down occurs 21 AL1L For High and low...

Page 9: ...SE br Range 1 to 9999 engineering units Note For other details see 24 HAL1 parameter 32 AL2d Alarm 2 delay Available When 26 AL2t type is different form nonE Range From oFF 0 to 9999 seconds Note The...

Page 10: ...ilable always but it is a read only parameter Range from 00 00 to 99 59 HH mm 42 Hi maximum measured value Available Available when 33 Hi Lo Hi high limit but it is a read only parameter Range Enginee...

Page 11: ...a set point equal to the minimum value of the operative range e g 10 C When the temperature in the chamber is steady take note of the temperature measured by the reference system e g 9 C 3 Set 50 A L...

Page 12: ...Exceeded indication EX OUT PK HI AL1 AL2 TC10 L Output b c d e The HI lamp d is ON When a measured value a is higher then the set point b EX lamp e lights OUT lamp b turns ON and the limit output rel...

Page 13: ...onds 2 The upper display will show PASS while the lower display will show 0 3 By and buttons set the value assigned to 44 PAS2 Level 2 password Notes 1 The factory default password for configuration p...

Page 14: ...n EN584 1 DIN 43710 1977 TC Type Ranges J 50 to 1000 C 50 0 to 999 9 C 58 to 1832 F 58 0 to 999 9 F K 50 to 1370 C 50 0 to 999 9 C 58 to 2498 F 58 0 to 999 9 F S 50 to 1760 C 50 0 to 999 9 C 58 to 320...

Page 15: ...arm output Available ever Type SSR drive Isolation Not isolated Protection Output protected from short circuit Stato logico 1 12 V 20 23 mA Stato logico 0 0 5 V Auxiliary power supply for TX NOTE this...

Page 16: ...ufacturing defects or faulty materials that are found within 18 months from manufacturing date The warranty is limited to the replacement of the instrument The tampering of the instrument or an improp...

Page 17: ...ms behaviour 0 oFF to 20 0 s 1 7 bS PV input bias 100 to 100 of the input span dP 8 di A Digital Input action 0 DI1 direct 1 DI1 reverse OUT group N Param Description Range value or selection list ele...

Page 18: ...Group N Param Description Range value or selection list elements Decimal gure 26 AL2t Alarm 2 type nonE Alarm not used LoAb Absolute low alarm HiAb Absolute high alarm LHAo Absolute band alarm with a...

Page 19: ...tion Range value or selection list elements Decimal gure 44 PAS2 Password level 2 0 oFF to 200 0 45 PAS3 Password level 3 3 to 200 0 46 di CL Display color 0 The display color is used to show the Exce...

Page 20: ...Yokogawa Electric Corporation TC10 L ENGINEERING MANUAL PAG 20...

Reviews: