2-10
IM 04L51B01-41EN
Communication (Serial) Settings
1
From the setting menu, select
Communication (Serial) settings
.
2
Select
Basic settings
. Set the following setup items. When you are finished, select
Save
.
Setup item
Value
Receiver
Function
Modbus master
Address
10
Data transfer*
Baud rate
115200
Parity bit
None
Stop bit
1 bit
* Please do not change the settings.
3
Select the Back icon (
), or select
Communication (Serial) settings
.
4
Select
Modbus master
and then
Basic settings
. Set the following setup items. When
you are finished, select
Save
.
Setup item
Value
Master function
On/Off
On
Communication
Interval*
1 s
Communication timeout
1 s
Gap between messages
Off
Recovery action
Retry
Once
Wait time
5 s
* Refer to “[Reference] Simple Calculation Method of Data Acquisition Interval” in
section 5.4.5, “Monitoring Unit Time of Radio Transmission,” of appendix 5.
5
Select the Back icon (
), or select
Communication (Serial) settings
.
6
Select
Modbus master
and then
Command settings
. Set the following setup items.
When you are finished, select
Save
.
Setup item
Value
Master command number
1
Command settings
Type
Read
Slave
1
Data type
INT16
Register
40003
Channel type
Communication channel
First-CH
0001
Last-CH
0001
Operation complete
Communication Channel Settings
1
From the setting menu, select Communication channel settings.
2
Set
On/Off, Span
. Set the following setup items. When you are finished, select
Save
.
If a message “Please set as recording channel” appears, select the close icon ( ).
Setup item
Value
First-CH
C001
Last-CH
C001
On/Off, Span
On/Off
On
Decimal place
1
Span lower
0.0
Span Upper
100.0
Unit
°C
Operation complete
2.1 Configuration