1
2
3
4
5
10
App
The following window appears.
3. Specify the COM port that the sender wireless communication module is connected to.
Click the COM port drop-down list, select the COM port that the wireless communication
module is connected to, and then click
Open
.
4. Specify the channel for sending radio signals.
To use the channel number set in the wireless communication module, click
Load from
module
. To specify a new channel, click the
Radio channel number
list, select the
channel number, and then click
Save to module
.
● The same channel number must be set on the second wireless communication module
(receiver), so take a note of this channel number.
● The channel number you specify here is the channel number for communication testing.
Setting the channel number in the wireless communication module here will not change
the settings in normal mode.
5. When configuration is complete, click
Close
to close the COM port, and then click
×
to
close the Communication test (Sender) window.
This completes the configuration of the first wireless communication module for
communication test (sender). The module is already sending radio signals.
Next, set the second wireless communication module to communication test mode
(receiver).
Setting the second wireless communication module to communication test
mode (receiver)
Set the second wireless communication module to communication test mode (receiver) by
following the procedure below. In communication tests, the wireless communication module
configured to be the receiver performs the measurements.
1. Perform the procedure explained in “Switching the wireless communication module to
measurement mode,” to switch to measurement mode.
Connect the wireless communication module that will be configured as the receiver, and
then set the measurement tool type to
Communication test mode (Receiver)
to switch
the measurement mode.
Note
• After changing to measurement mode, do not perform any operation other than starting the
communication test (sender) tool. To perform other operations, set the wireless communication
module back to normal mode by executing step 4 in “Performing a communication test” first.
• If you turn off the module in measurement mode, the module will start in the selected
measurement mode the next time the power is turned on.