IM MY600-01EN
7. Low-Resistance Measurement
(Continuity Check)
WARNING
Do not apply voltage in the low-resistance measurement
range. Check that the power is not running through the
circuit under test before making a measurement.
French
AVERTISSEMENT
Ne pas appliquer de tension à la plage de faible résistance.
Toujours vérifier le circuit ou l’équipement sous test est
désactivé de manière sûre avant de commencer une
mesure.
0Ω Adjustment Function
The 0Ω adjustment function cancels the resistances of the
probe and fuse to display only the resistance of the DUT.
Up to about 3 Ω of resistance can be cancelled.
Setup Procedure
1.
Set the range switch to the V/Ω position.
2.
If the instrument is set to voltage measurement
mode, press SELECT to change to low-resistance
measurement mode.
3.
Short the red probe connected to the LINE terminal and
the black probe connected to the EARTH terminal.