<12. Parameter Lists>
12-1
IM 01S01C01-01EN
12. Parameter Lists
Note: The Write Mode column contains the modes in which each parameter is write enabled.
O/S: Write enabled in O/S mode.
MAN: Write enabled in Man mode and O/S mode.
AUTO: Write enabled in Auto mode, Man mode, and O/S mode.
12.1 Resource Block
Relative
Index Index
Parameter Name
Factory Default
Write
Mode
Explanation
0
1000
Block Header
TAG:“RS”
Block
Tag
=O/S
Information on this block such as Block Tag, DD Revision,
Execution Time etc.
1
1001
ST_REV
—
—
The revision level of the static data associated with the
resource block. The revision value is incremented each
time a static parameter value in this block is changed.
2
1002
TAG_DESC
Null
AUTO
The user description of the intended application of the
block.
3
1003
STRATEGY
0
AUTO
The strategy field can be used to identify grouping of
blocks. This data is not checked or processed by the block.
4
1004
ALERT_KEY
0
AUTO
The identification number of the plant unit. This information
may be used in the host for sorting alarms, etc.
5
1005
MODE_BLK
AUTO
AUTO
The actual, target, permitted, and normal modes of the
block.
6
1006
BLOCK_ERR
—
—
This parameter reflects the error status associated with the
hardware or software components associated with a block.
It is a bit string, so that multiple errors may be shown.
7
1007
RS_STATE
—
—
State of the resource block state machine.
8
1008
TEST_RW
Null
AUTO
Read/write test parameter-used only for conformance
testing and simulation.
9
1009
DD_RESOURCE
Null
—
String identifying the tag of the resource which contains the
Device Description for this resource.
10
1010
MANUFAC_ID
0x00594543
—
Manufacturer identification number-used by an interface
device to locate the DD file for the resource.
11
1011
DEV_TYPE
16
—
Manufacturer’s model number associated with the
resourceused by interface devices to locate the DD file for
the resource.
12
1012
DEV_REV
1
—
Manufacturer revision number associated with the
resourceused by an interface device to locate the DD file
for the resource.
13
1013
DD_REV
1
—
Revision of the DD associated with the resource-used by
an interface device to locate the DD file for the resource.
14
1014
GRANT_DENY
0
AUTO
Options for controlling access of host computer and local
control panels to operating, tuning and alarm parameters
of the block.
15
1015
HARD_TYPES
Scalar input
—
The types of hardware available as channel numbers.
bit0: Scalar input
bit1: Scalar output
bit2: Discrete input
bit3: Discrete output
16
1016
RESTART
—
—
Allows a manual restart to be initiated. Several degrees of
restart are possible. They are 1: Run, 2: Restart resource,
3: Restart with initial value specified in FF functional spec.
(*1), and 4: Restart processor.
*1: FF-891 Foundation
TM
Specification Function Block
Application Process Part 2.
17
1017
FEATURES
Reports
Fault state
Soft W Lock
Hard W Lock
Multi_bit Alarm support
—
Used to show supported resource block options.
18
1018
FEATURE_SEL
Report
Fault state
Soft W Lock
AUTO
Used to select resource block options defined in
FEATURES.
bit0: Scheduled
bit1: Event driven
bit2: Manufacturer specified
Summary of Contents for FVX110
Page 1: ...User s Manual FVX110 Fieldbus Segment Indicator IM 01S01C01 01EN IM 01S01C01 01EN 4th Edition ...
Page 15: ... 2 Handling Cautions 2 4 IM 01S01C01 01EN ...
Page 16: ... 2 Handling Cautions 2 5 IM 01S01C01 01EN ...
Page 17: ... 2 Handling Cautions 2 6 IM 01S01C01 01EN ...
Page 18: ... 2 Handling Cautions 2 7 IM 01S01C01 01EN ...
Page 19: ... 2 Handling Cautions 2 8 IM 01S01C01 01EN ...