<2. Handling Cautions>
2-10
IM 01S01C01-01EN
2.8.2 CSA Certification
a. CSA Explosionproof Type
Caution for CSA explosionproof type.
Note 1. FVX110 Fieldbus Segment Indicator with
optional code /CF1 is applicable for use in
hazardous locations:
Certificate: 2325751
• Applicable Standard:
C22.2 No.0, C22.2 No.0.4, C22.2 No.0.5,
C22.2 No.25, C22.2 No.30, C22.2 No.94,
C22.2 No.61010-01-04, C22.2 No.60079-0,
C22.2 No.60079-1
[For CSA C22.2]
•
Explosion-proof for Class I, Groups B, C and
D.
•
Dustignition-proof for Class II/III, Groups E, F
and G.
•
Enclosure: TYPE 4X
•
Temperature Code: T6
[For CSA E60079]
•
Flameproof for Zone 1, Ex d IIC T6
•
Enclosure: IP66 / IP67
•
Ambient Temperature: –50* to 75ºC (T6)
* –15ºC when O-ring material is Fluoro-rubber.
•
Supply Voltage: 32 V dc max.
•
Output Signal: 15 mA dc
Note 2. Wiring
•
All wiring shall comply with Canadian
Electrical Code Part I and Local Electrical
Codes.
•
In hazardous location, wiring shall be in
conduit as shown in the figure.
•
WARNING:
A SEAL SHALL BE INSTALLED WITHIN
50cm OF THE ENCLOSURE.
UN SCELLEMENT DOIT ÊTRE INSTALLÉÀ
MOINS DE 50cm DU BOîTIER.
•
WARNING:
WHEN INSTALLED IN CL.I, DIV 2, SEAL
NOT REQUIRED.
UNE FOIS INSTALLÉ DANS CL I, DIV 2,
AUCUN JOINT N'EST REQUIS.
Note 3. Operation
•
WARNING:
AFTER DE-ENERGIZING, DELAY 5
MINUTES BEFORE OPENING.
APRÉS POWER-OFF, ATTENDRE 5
MINUTES AVANT D'OUVRIR.
•
WARNING:
WHEN AMBIENT TEMPERATURE ≥ 65ºC,
USE THE HEAT-RESISTING CABLES ≥
90ºC.
QUAND LA TEMPÉRATURE AMBIANTE
≥ 65ºC, UTILISEZ DES CÂBLES
RÉSISTANTES Á LA CHALEUR ≥ 90ºC.
•
Take care not to generate mechanical
sparking when accessing to the instrument
and peripheral devices in a hazardous
location.
Note 4. Maintenance and Repair
• The instrument modification or parts
replacement by other than authorized
representative of Yokogawa Electric
Corporation and Yokogawa Corporation of
America is prohibited and will void Canadian
Standards Explosionproof Certification.
Non-hazardous
Location
Equipment
32 V DC Max.
15 mA DC
Signal
Non-Hazardous
Locations
Hazardous Locations Division 1
Non-Hazardous
Locations
Hazardous Locations Division 2
50 cm Max.
Sealing Fitting
Conduit
Non-hazardous
Location
Equipment
32 V DC Max.
15 mA DC
Signal
Sealing Fitting
F0206.ai
SUPPLY
PULSE
CHECK
ALARM
SUPPLY
PULS
E
CHECK
ALARM
Segment Indicator
Segment Indicator
b. CSA Intrinsically safe and Nonincendive
Type
FVX110 Fieldbus Segment Indicator with
optional code /CS15.
• Certificate: 2422326
• Applicable standard:
C22.2 No.0, C22.2 No.0.4, C22.2 No.25,
CAN/CSA C22.2 No.94,
CAN/CSA C22.2 No.157, C22.2 No.213,
CAN/CSA C22.2 No.61010-1-04,
CAN/CSA C22.2 No.60079-0,
CAN/CSA E60079-11,
CAN/CSA E60079-15, IEC 60529
Summary of Contents for FVX110
Page 1: ...User s Manual FVX110 Fieldbus Segment Indicator IM 01S01C01 01EN IM 01S01C01 01EN 4th Edition ...
Page 15: ... 2 Handling Cautions 2 4 IM 01S01C01 01EN ...
Page 16: ... 2 Handling Cautions 2 5 IM 01S01C01 01EN ...
Page 17: ... 2 Handling Cautions 2 6 IM 01S01C01 01EN ...
Page 18: ... 2 Handling Cautions 2 7 IM 01S01C01 01EN ...
Page 19: ... 2 Handling Cautions 2 8 IM 01S01C01 01EN ...