<Appendix 5. PID Block>
A5-2
IM 01S01C01-01EN
A5.3 Parameters of PID Block
NOTE: In the table below, the Write column shows the modes in which the respective parameters can be
written. A blank in the Write column indicates that the corresponding parameter can be written in all modes of
the PID block. A dash (-) indicates that the corresponding parameter cannot be written in any mode.
Index Index
PID1
Index
PID2
Parameter
Name
Default
(factory setting)
Write
Valid Range
Description
0
8000
8100 Block Header
TAG: “PID”
Block Tag
= O/S
Information on this block such as Block
Tag, DD Revision, Execution Time etc.
1
8001
8101 ST_REV
—
The revision level of the static data
associated with the function block. The
revision value will be incremented each
time a static parameter value in the
block is changed.
2
8002
8102 TAG_DESC
Null
The user description of the intended
application of the block.
3
8003
8103 STRATEGY
1
The strategy field can be used to
identify grouping of blocks. This data is
not checked or processed by the block.
4
8004
8104 ALERT_KEY
1
1 to 255
The identification number of the plant
unit. This information may be used in
the host for sorting alarms, etc.
5
8005
8105 MODE_BLK
A universal parameter that represents
block operating condition. It comprises
the Actual, Target, Permit and Normal
modes.
6
8006
8106 BLOCK_ERR
—
This parameter reflects the error
status associated with the hardware or
software components associated with
a block. It is a bit string, so that multiple
errors may be shown.
7
8007
8107 PV
—
Measured value; the non-dimensional
value that is converted from the input
(IN) value based on the PV_SCALE
values and filtered.
8
8008
8108 SP
0
AUTO
PV_SCALE ±10%
Setpoint
9
8009
8109 OUT
MAN
Output
10
8010
8110 PV_SCALE
100
0
1342
1
O/S
Upper and lower scale limit values used
for scaling of the input (IN) value.
11
8011
8111 OUT_SCALE
100
0
1342
1
O/S
Upper and lower scale limit values used
for scaling of the control output (OUT)
value to the values in the engineering
unit.
12
8012
8112 GRANT_DENY
0
AUTO
Options for controlling access of host
computers and local control panels to
operating, tuning and alarm parameters
of the block.
13
8013
8113 CONTROL_
OPTS
0
O/S
Setting for control action. See Section
A5.13 for details.
14
8014
8114 STATUS_OPTS
0
O/S
See Section A5.15 for details.
15
8015
8115 IN
0
Controlled-value input.
16
8016
8116 PV_FTIME
2
AUTO
Non-negative
Time constant (in seconds) of the first-
order lag filter applied to IN.
17
8017
8117 BYPASS
1 (off)
MAN
1, 2
Whether to bypass the control
computation.
1 (off): Do not bypass.
2 (on): Bypass.
18
8018
8118 CAS_IN
0
Cascade setpoint
19
8019
8119 SP_RATE_DN
+INF
Positive
Rate-of-decrease limit for setpoint (SP).
20
8020
8120 SP_RATE_UP
-INF
Positive
Rate-of-increase limit for setpoint (SP).
21
8021
8121 SP_HI_LIM
100
PV_SCALE ±10%
Upper limit for setpoint (SP).
Summary of Contents for FVX110
Page 1: ...User s Manual FVX110 Fieldbus Segment Indicator IM 01S01C01 01EN IM 01S01C01 01EN 4th Edition ...
Page 15: ... 2 Handling Cautions 2 4 IM 01S01C01 01EN ...
Page 16: ... 2 Handling Cautions 2 5 IM 01S01C01 01EN ...
Page 17: ... 2 Handling Cautions 2 6 IM 01S01C01 01EN ...
Page 18: ... 2 Handling Cautions 2 7 IM 01S01C01 01EN ...
Page 19: ... 2 Handling Cautions 2 8 IM 01S01C01 01EN ...