<Appendix 3. Input Selector (IS) Block>
A3-11
IM 01S01C01-01EN
When SELECT TYPE is “Average”
The block calculates the average of the valid inputs and transmits it to OUT. The number of inputs used to
calculate its value is indicated in SELECTED.
SELECTION
IN_1 = 23
SELECT_TYPE = Average
STATUS_OPTS
MIN_GOOD = 1
SELECTED = 8
OUT = 25.48
(IN_1+···+IN_8)/8 = 25.48
IN_2 = 34.5
IN_3 = 45
IN_4 = 2.34
IN_5 = 23.6
IN_6 = 15.5
IN_7 = 32.5
IN_8 = 27.4
DISABLE_1 = OFF
DISABLE_2 = OFF
DISABLE_3 = OFF
DISABLE_4 = OFF
DISABLE_5 = OFF
DISABLE_6 = OFF
DISABLE_7 = OFF
DISABLE_8 = OFF
OP_SELECT = 0
FA0309.ai
Figure A3.9 Example (8)
When SELECT TYPE is “Latched Good”
The valid input with the smaller input number is selected as an output and is held until it becomes invalid.
When it becomes invalid, the next valid input will be selected as an output regardless of the magnitude of the
value. Even if an input with the input number smaller than that of the currently selected input recovers, the
current selection is held.
Assuming that IN_2 is the valid input with the smallest input number, the order of input selection is IN_2 →
IN_3 → ...→ IN_8 → IN_1 → ....
If the power is turned OFF and then ON with SELECT TYPE set to “Latched Good,” input selection starts with
the IN that was selected before the power was turned OFF.
Summary of Contents for FVX110
Page 1: ...User s Manual FVX110 Fieldbus Segment Indicator IM 01S01C01 01EN IM 01S01C01 01EN 4th Edition ...
Page 15: ... 2 Handling Cautions 2 4 IM 01S01C01 01EN ...
Page 16: ... 2 Handling Cautions 2 5 IM 01S01C01 01EN ...
Page 17: ... 2 Handling Cautions 2 6 IM 01S01C01 01EN ...
Page 18: ... 2 Handling Cautions 2 7 IM 01S01C01 01EN ...
Page 19: ... 2 Handling Cautions 2 8 IM 01S01C01 01EN ...