<12. Parameter Lists>
12-5
IM 01S01C01-01EN
Relative
Index Index
Parameter Name
Factory Default
Write
Mode
Explanation
4
2004
ALERT_KEY
1
AUTO
Key information used to identify the location at which an
alert occurred. Generally, this parameter is used by a
high-level system to identify specific areas in a plant that
are under the control of specific operators to distinguish
necessary alarms only. This is a universal parameter.
5
2005
MODE_BLK
AUTO
AUTO
A universal parameter that represents block operating
condition. It comprises the Actual, Target, Permit and
Normal modes.
6
2006
BLOCK_ERR
-
AUTO
Indicates error status of the PID block. The FVX110
transducer block handles the following factors.
Bit 0 = An XD_ERROR has occurred
Bit 15 = Target mode is O/S
7
2007
UPDATE_EVT
-
AUTO
Indicates event information if an event update occurs.
8
2008
BLOCK_ALM
-
AUTO
Indicates error information if an error occurs in a block.
9
2009
TRANSDUCER_
DIRECTORY
-
AUTO
Parameter for storing indexes of FVX110 transducers.
10
2010
TRANSDUCER_TYPE 65535
AUTO
Indicates FVX110 types.
Indicates 65535 (other) for the FVX110.
11
2011
XD_ERROR
0
AUTO
Stores the most serious errors that occur in the transducer
block.
0 = No error
50 = Reset performed
100 = LCD error
12
2012
COLLECTION_
DIRECTORY
AUTO
Stores the DD item ID for the first index of important
parameters in the LCD transducer block.
13
2013
NOW_DISPLAYING
0
AUTO
Indicates the number that the input currently displayed on
the LCD occupies among valid inputs of information.
14
2014
DISP_TARGET_
FORCE
0
AUTO
A parameter for identifying information of valid inputs that
you want to view
0: Scroll knob is active
1: No.01 in valid connection
2: No.02 in valid connection
3: No.03 in valid connection
4: No.04 in valid connection
5: No.05 in valid connection
6: No.06 in valid connection
7: No.07 in valid connection
8: No.08 in valid connection
9: No.09 in valid connection
10: No.10 in valid connection
11: No.11 in valid connection
12: No.12 in valid connection
13: No.13 in valid connection
14: No.14 in valid connection
15: No.15 in valid connection
16: No.16 in valid connection
15
2015
NO_OF_VALID_CON 0 (Soft Rev 1.02 or
earlier)
1 (Soft Rev 1.04 or
later)
AUTO
Indicates how many of the 16 inputs are valid.
(Corresponds to the denominator when DISP_PAGE_
INFO is displayed.)
16
2016
VALID_CON_
SUMMARY
0xFFFF (Soft Rev
1.02 or earlier)
0x0001 (Soft Rev
1.04 or later)
AUTO
Sets which of the 16 inputs are valid inputs.
17
2017
MAO_CON_
SUMMARY
0x0000
AUTO
Indicates which of the 16 inputs gets MAO block values.
18
2018
ISEL_CON_
SUMMARY
0x0000 (Soft Rev
1.02 or earlier)
0x0001 (Soft Rev
1.04 or later)
AUTO
Indicates which of the 16 inputs gets IS block values.
19
2019
SIM_CON_
SUMMARY
0xFFFF (Soft Rev
1.02 or earlier)
0xFFFE (Soft Rev
1.04 or later)
AUTO
Indicates which of the 16 inputs gets Simulation state
values.
20
2020
BAR_GRAPH_
SELECT
0
AUTO
Use to specify whether bar graphs should be displayed in
the lower field of the LCD. (16 input batch setting)
21
2021
EACH_BAR_GRAPH 0x0000
AUTO
Use to specify whether bar graphs should be displayed in
the lower field of the LCD. (Each input batch setting)
Summary of Contents for FVX110
Page 1: ...User s Manual FVX110 Fieldbus Segment Indicator IM 01S01C01 01EN IM 01S01C01 01EN 4th Edition ...
Page 15: ... 2 Handling Cautions 2 4 IM 01S01C01 01EN ...
Page 16: ... 2 Handling Cautions 2 5 IM 01S01C01 01EN ...
Page 17: ... 2 Handling Cautions 2 6 IM 01S01C01 01EN ...
Page 18: ... 2 Handling Cautions 2 7 IM 01S01C01 01EN ...
Page 19: ... 2 Handling Cautions 2 8 IM 01S01C01 01EN ...