<Appendix 5. PID Block>
A5-3
IM 01S01C01-01EN
Index Index
PID1
Index
PID2
Parameter
Name
Default
(factory setting)
Write
Valid Range
Description
22
8022
8122 SP_LO_LIM
0
PV_SCALE ±10%
Lower limit for setpoint (SP).
23
8023
8123 GAIN
1
Proportional gain (= 100 / proportional
band).
24
8024
8124 RESET
10
Integration time (seconds).
25
8025
8125 BAL_TIME
0
Positive
Unused
26
8026
8126 RATE
0
Positive
Derivative time (seconds).
27
8027
8127 BKCAL_IN
0
Read-back of control output.
28
8028
8128 OUT_HI_LIM
100
OUT_SCALE ±10% Upper limit for control output (OUT).
29
8029
8129 OUT_LO_LIM
0
OUT_SCALE ±10% Lower limit for control output (OUT).
30
8030
8130 BKCAL_HYS
0.5 (%)
0 to 50%
Hysteresis for release from a limit for
OUT.status.
31
8031
8131 BKCAL_OUT
0
—
Read-back value to be sent to the
BKCAL_IN in the upper block.
32
8032
8132 RCAS_IN
0
Remote setpoint set from a computer,
etc.
33
8033
8133 ROUT_IN
0
Remote control output value set from a
computer, etc.
34
8034
8134 SHED_OPT
0
Action to be performed in the event of
mode shedding.
SHED_OPT defines the changes to
be made to MODE.BLK.target and
MODE.BLK.actual when the value of
RCAS_IN.status or ROUT_IN.status
becomes Bad if MODE_BLK.actual =
RCas or ROut.
See Section A5.17.1 for details.
35
8035
8135 RCAS_OUT
0
—
Remote setpoint sent to a computer,
etc.
36
8036
8136 ROUT_OUT
0
—
Remote control output value.
37
8037
8137 TRK_SCALE
100
0
1342
1
MAN
Upper and lower scale limits used
to convert the output tracking value
(TRK_VAL) to non-dimensional.
38
8038
8138 TRK_IN_D
0
Switch for output tracking. See Section
A5.12 for details.
39
8039
8139 TRK_VAL
0
Output tracking value (TRK_VAL).
When MODE_BLK.actual = LO, the
value scaled from the TRK_VAL value
is set in OUT.
40
8040
8140 FF_VAL
0
Feedforward input value.
The FF_VAL value is scaled to a
value with the same scale as for OUT,
multiplied by the FF_GAIN value, and
then added to the output of the PID
computation.
41
8041
8141 FF_SCALE
100
0
1342
1
MAN
Scale limits used for converting the
FF_VAL value to a non-dimensional
value.
42
8042
8142 FF_GAIN
0
MAN
Gain for FF_VAL.
43
8043
8143 UPDATE_EVT
—
This alert is generated by any change
to the static data.
44
8044
8144 BLOCK_ALM
—
The block alarm is used for all
configuration, hardware, connection
failure or system problems in the block.
The cause of the alert is entered in
the subcode field. The first alert to
become active will set the Active status
in the Status attribute. As soon as the
Unreported status is cleared by the alert
reporting task, another block alert may
be reported without clearing the Active
status, if the subcode has changed.
Summary of Contents for FVX110
Page 1: ...User s Manual FVX110 Fieldbus Segment Indicator IM 01S01C01 01EN IM 01S01C01 01EN 4th Edition ...
Page 15: ... 2 Handling Cautions 2 4 IM 01S01C01 01EN ...
Page 16: ... 2 Handling Cautions 2 5 IM 01S01C01 01EN ...
Page 17: ... 2 Handling Cautions 2 6 IM 01S01C01 01EN ...
Page 18: ... 2 Handling Cautions 2 7 IM 01S01C01 01EN ...
Page 19: ... 2 Handling Cautions 2 8 IM 01S01C01 01EN ...