B2-4
IM 34M06H63-01E
2nd Edition : Jul.16,2015-00
B2.2.1 Common Process Data
These are representative process-related data for all channels. It consolidates in a single
data area process-related data such as process value, operating status and error status.
Table B2.3 Common Process Data
Data
Position
Number
Symbol
Description
Unit Data
Range
Default
Value
Attribute Stored
See
Also
Process
Value
1
PV.1
Process
value
Industrial
unit
-5.0 to 105.0% of
(PRL to PRH)
RO
C2.
2
PV.2
RO
3
PV.3
RO
4
PV.4
RO
Operating
Status
41
RUN.STUS.1 Operating
status
None
Each bit is on or off
depending on the status of
the operating status.
For details, see text section
under “See Also”
RO
B2.2.5
42
RUN.STUS.2
RO
43
RUN.STUS.3
RO
44
RUN.STUS.4
RO
Error
Status
51
ERR.STUS.1 Error status
None
Each bit is on or off
depending on the error
status.
For details, see text section
under “See Also”.
RO
C5.
52
ERR.STUS.2
RO
53
ERR.STUS.3
RO
54
ERR.STUS.4
RO
B2.2.2 Setup Control Parameters
Use these parameters to enable various settings, required when monitoring parameters
and input parameters are updated. For details on the procedure, see Section B2.3, “How
to Enable Settings”.
Table B2.4 Setup Control Parameters
Data
Position
Number
Symbol
Description
Unit
Data Range
Default
Value
Attribute Stored
See
Also
71 SETUP
Setup
None 0: Disable setup instruction operand;
1: Enable setup instruction operand
0
RW
B2.3
72
OPE Setup instruction
operand
None 1, 2, 4, 8or 16. For details, see Table
B2.5.
0
RW
73
STUS Setup instruction
response
None 0: No error; or data position number of
error register
0
RO
Table B2.5 Setup Instruction Operand (OPE) Values
Preset
Value
Description Explanation
1
Initialize all parameters
Reverts all parameters to their factory settings.
*1
2 Enable
monitoring
parameters
Enables the monitoring parameters, which are the most basic setup elements.
The module initializes input parameters and operation parameters based on the monitoring
parameter values.
4 Enable
input
type
settings
Enables the Input Type Selection parameter.
The module initializes input range settings, PV range settings and Operation parameters based on
the input type selection parameter value.
8 Enable
input
range
settings
Enables the input range settings.
The module initializes PV range settings and operation parameters based on these settings.
16
Enable PV range
settings
Enables the PV range settings, which are required only in Two-input Changeover mode.
The module initializes operation parameters based on these settings.
*1
Input type and power supply frequency selection defined by the hardware switches have precedence over software
settings.
Writing to the Setup Instruction Operand (OPE) register a preset value that is not listed in
Table B2.5, “Setup Instruction Operand Values,” has no effect on module operation. When
the setup operation completes, the Setup Instruction Operand (OPE) register resets to 0.
CAUTION
Summary of Contents for FA-M3 VITESSE F3CX04-0N
Page 2: ...Blank Page...
Page 16: ...Blank Page...
Page 18: ...Blank Page...
Page 32: ...Blank Page...
Page 44: ...Blank Page...
Page 68: ...Blank Page...
Page 80: ...Blank Page...
Page 82: ...Blank Page...
Page 90: ...Blank Page...
Page 110: ...Blank Page...
Page 118: ...Blank Page...
Page 126: ...Blank Page...
Page 128: ...Blank Page...
Page 132: ...Blank Page...
Page 142: ...Blank Page...
Page 144: ...Blank Page...