D2-2
IM 34M06H63-01E
1st Edition : July, 2003-00
(1) Input does not change, or fluctuates excessively
If input does not change, or fluctuates excessively, there may be a problem with sensor
connection, module usage, or register preset values. Follow the steps below to locate the
cause.
- Confirm that the sensor is securely and correctly connected.
- Confirm that the registers are correctly set. See the table below.
Data Position Number
Symbol
Content
Check Items
See Also
Loop1 Loop2 Loop3 Loop4
71
SETUP
Setup
Is SETUP set to 1?
It must be set to 0.
B2.3
81
FREQ
Power supply frequency
selection
Is FREQ correctly set to match the frequency of
the power supply used?
It must be correctly set.
B3.1.1
82
SMP
Input sampling period
Is the channel whose input does not change
available for use?
To use channels 3 and 4, Input sampling period
should be set to 200 ms.
B3.1.2
83
MD12
Monitoring mode
Is the channel whose input does not change
available for use?
If the channel set to ‘disabled’, enable it.
B3.1.3
84
MD34
142 342 542
742
IN
Input type selection
Is the input type appropriate for the sensor type
used?
Set the input type to match the sensor used.
B3.2.1
172 372 572
772
FL
Input filter
Is excessive noise interfering with the input?
Set FL to an appropriate value.
C2.10
Summary of Contents for FA-M3 VITESSE F3CX04-0N
Page 2: ...Blank Page...
Page 16: ...Blank Page...
Page 18: ...Blank Page...
Page 32: ...Blank Page...
Page 44: ...Blank Page...
Page 68: ...Blank Page...
Page 80: ...Blank Page...
Page 82: ...Blank Page...
Page 90: ...Blank Page...
Page 110: ...Blank Page...
Page 118: ...Blank Page...
Page 126: ...Blank Page...
Page 128: ...Blank Page...
Page 132: ...Blank Page...
Page 142: ...Blank Page...
Page 144: ...Blank Page...