A2.7 Components and Functions
CX04-0N
RDY
ALM
ERR
60Hz
IN3
IN4
IN1
IN2
F3CX04-0N
MONITOR
A
b
B
A
b
B
Status Indicators
RDY (green)
Lit when the internal circuit is functioning
normally. Turns off when an error occurs in
the module.
60 Hz (green)
Indicates the frequency of the commercial
power supply,
On: 60Hz; Off: 50 Hz.
ALM (orange)
Lit when an alarm occurs in any channel.
ERR (red)
Lit or flashes when a hardware failure is
detected or an error is detected in stored
data.
Lit when an error is detected in system data,
calibration values, ADC, RJC or EEPROM.
Flashes when an invalid input, monitoring or
operation parameter is detected or a burnout
is detected.
Input terminal block
18-point detachable terminal block with M3.5
screws.
Figure A2.1
F3CX04-0N Front View
Note: This is the right side view of the module with its cover removed .
SW5: Input type selector switch
(Input type is determined by the
combined values of SW1-3, SW1-4, and SW5.)
SW1-1: Temperature unit selector switch
SW1-2: Power frequency selector switch
SW1-3: Input type selector switch
SW1-4: Input type selector switch
Figure A2.2 Right Side View Showing Input Type and Power Supply Frequency Selector
Switches
CAUTION
You may switch the temperature unit between
C and
F using SW1-1. For details, see
Section C6, “Selecting Temperature Unit.”
Summary of Contents for FA-M3 VITESSE F3CX04-0N
Page 2: ...Blank Page...
Page 16: ...Blank Page...
Page 18: ...Blank Page...
Page 32: ...Blank Page...
Page 44: ...Blank Page...
Page 68: ...Blank Page...
Page 80: ...Blank Page...
Page 82: ...Blank Page...
Page 90: ...Blank Page...
Page 110: ...Blank Page...
Page 118: ...Blank Page...
Page 126: ...Blank Page...
Page 128: ...Blank Page...
Page 132: ...Blank Page...
Page 142: ...Blank Page...
Page 144: ...Blank Page...