B1.3 Writing and Reading After Powering On
Do not read and write to output data registers before module startup completes. This can
be ensured by checking that the MDLRDY relay is set.
Table B1.4 Relays Relating to Writing and Writing After Powering On
Input Relay Number
X
nn
*1
Symbol
Description
Data Values
X16
MDLRDY
Module startup has completed
0: During startup,
1: Startup completed
*1:
denotes the slot number where the module is installed.
Figure B1.2 Checking for Module Startup Completion after Powering On
After powering on, it takes up to approximately 2 seconds for the module startup to
complete (startup initialization). Any data written during this period may be ignored. For
instance, if a write instruction to the special relay M35, “On for 1 Scan after Startup” is
used in a sequence program to start a program after powering on, the written data may be
ignored.
If data is written before the MDLRDY relay turns on, such data may be overwritten during
module initialization. If the write destination is a stored parameter, the data may be
overwritten by the stored data; if the write destination is a non-stored parameter, the data
may be overwritten by the default value.
Similarly, if data is read before the MDLRDY relay is set, the data read may be invalid.
Summary of Contents for FA-M3 VITESSE F3CX04-0N
Page 2: ...Blank Page...
Page 16: ...Blank Page...
Page 18: ...Blank Page...
Page 32: ...Blank Page...
Page 44: ...Blank Page...
Page 68: ...Blank Page...
Page 80: ...Blank Page...
Page 82: ...Blank Page...
Page 90: ...Blank Page...
Page 110: ...Blank Page...
Page 118: ...Blank Page...
Page 126: ...Blank Page...
Page 128: ...Blank Page...
Page 132: ...Blank Page...
Page 142: ...Blank Page...
Page 144: ...Blank Page...