C2-12
IM 34M06H63-01E
1st Edition : July, 2003-00
C2.6
Reference Junction Compensation
If an external reference point device is used to provide better reference junction
compensation, set Reference Junction Compensation to ‘Fixed Value’, and set Reference
Junction Temperature.
Table C2.10 Reference Junction Compensation Parameters
Data Position Number
Symbol Description
Unit Data
Range
Default
Value
Attribute Stored
CH1 CH2 CH3 CH4
149 349 549 749 RJC Reference
junction
compensation setting
None
0: Fixed value
1: ON
1 RW
132 332 532 732 EXRJC Reference
junction
temperature
(valid when Reference
Junction
Compensation is set to
Fixed Value)
Industrial
unit
-100 to 700
(-10.0
C to
70.0
C)
0 RW
−