C5-4
IM 34M06H63-01E
1st Edition : July, 2003-00
Table C5.5 Operation Errors (2/2)
ERR.STUS
(bit position)
ERR
LED
Error Condition Monitor Operation Measurement
Trouble-
shooting
Status
11
Flashing PV burnout
Depends on BSL
burnout selection.
Depends on
BSL burnout
selection.
Check the
sensor and
sensor
circuit.
Proces
s error
12/13 Off
PV
OVER
PV = 105% or -5%
Limit values
Check the
process.
Undefined
Undefined Out of control
(due to abnormal
power supply or
noise)
CPU resets.
Undefined
If switching
off and on
does not
restore
normal
operation,
have the
module
repaired.
Hard
ware
failure