![YOKOGAWA DpharpEJX vigilantplant EJX910A User Manual Download Page 63](http://html1.mh-extra.com/html/yokogawa/dpharpejx-vigilantplant-ejx910a/dpharpejx-vigilantplant-ejx910a_user-manual_3750163063.webp)
IM 01C25R01-01E
10-8
10. GENERAL SPECIFICATIONS
Item
Description
Code
Painting
Color change
Coating change
Lightning protector
Calibration units
*3
Long vent
*4
Output limits
and failure operation
*5
P
X2
A
K1
D1
D3
D4
U1
C1
(See Table for Span and
Range Limits.)
Amplifier cover only
Anti-corrosion coating
*1
Degrease cleansing treatment
P calibration (psi unit)
bar calibration (bar unit)
M calibration (kgf/cm
2
unit)
Total length: 119 mm (standard: 34 mm); Total length when combining with option code
K1, K2, K5, and K6: 130 mm. Material: 316 SST
Failure alarm down-scale : Output status at CPU failure and hardware error is
$
2.5%, 3.6 mA DC or less.
K2
Degrease cleansing treatment and with fluorinated oilfilled capsule.
Operating temperature
$
20 to 80
#
C(
$
4 to 176
#
F)
Oil-prohibited use
*2
Material certificate
*8
Cover flange
*9
Cover flange, Process connector
*10
M01
M11
Pressure test/
Leak test certificate
*13
European Pressure
Equipment Directive
*15
Nitrogen(N
2
) Gas
*12
Retention time: one minute
K5
Degrease cleansing treatment and dehydrating treatment
K6
Degrease cleansing treatment and dehydrating treatment with fluorinated oilfilled capsule.
Operating temperature
$
20 to 80
#
C(
$
4 to 176
#
F)
Oil-prohibited use
with dehydrating treatment
*2
N1
Right side high pressure, without drain and vent plugs
Body option
*6
Data configuration at factory
*7
N2
N1 and Process connection, based on IEC61518 with female thread on both sides of
cover flange, with blind kidney flanges on back.
N3
N2, and Material certificate for cover flange, diaphragm, capsule body, and blind
kidney flange
Stainless steel tag plate
N4
T13
T12
304SST tag plate wired onto transmitter
T1013E.EPS
Transmitter power supply voltage: 10.5 to 32 V DC
Allowable current: Max. 6000 A ( 1
40
s ), Repeating 1000 A ( 1
40
s ) 100 times
Applicable Standards: IEC 61000-4-4, IEC 61000-4-5
Amplifier cover and terminal cover, Munsell 7.5 R4/14
PR
NAMUR NE43 Compliant
Output signal limits: 3.8 mA to
20.5 mA
Failure alarm down-scale: Output status at CPU
failure and hardware error is
$
2.5%, 3.6 mA DC or less.
Failure alarm up-scale: Output status at CPU
failure and hardware error is 110%, 21.6 mA or more.
C2
C3
Capsule fill fluid
K3
Fluorinated oil filled in capsule
Data configuration for HART communication type
PED 97/23/EC
Category III, Module H, Type of Equipment: Pressure Accessory-Vessel,
Type of Fluid: Liquid and Gas, Group of Fluid: 1 and 2
CA
PE3
Software damping,
Descriptor, Message
L
H
Terminal
side
Test Pressure: 25 MPa(3600 psi)
*11
Test Pressure: 16 MPa(2300 psi)
*14
*1:
Not applicable with color change option.
*2:
Applicable for Wetted parts material code S.
*3:
The unit of MWP (Max. working pressure) on the name plate of a housing is the same unit as specified by option codes D1,
D3, and D4.
*4:
Applicable for vertical impulse piping type (Installation code 7) and Wetted parts material code S.
*5:
Applicable for output signal codes E. The hardware error indicates faulty amplifier or capsule.
*6:
Applicable for wetted parts material code S; process connection codes 3, 4, and 5; installation code 9; and mounting bracket
code N. Process connection faces on the other side of zero adjustment screw.
*7:
Also see ‘Ordering Information’.
*8:
Material traceability certification, per EN 10204 3.1B.
*9:
Applicable for process connections codes 0 and 5.
*10:
Applicable for process connections codes 1, 2, 3, and 4.
*11:
Applicable for capsule codes M and H.
*12:
Pure nitrogen gas is used for oil-prohibited use (option codes K1, K2, K5, and K6).
*13:
The unit on the certificate is always Pa unit regardless of selection of option code D1, D3 or D4.
*14:
Applicable for capsule code L.
*15:
Applicable for measurement span code M and H. If compliance with category III is needed, specify this option code.