IM 01C25R01-01E
3-6
3. HANDLING CAUTIONS
Note 4. Maintenance and Repair
• The instrument modification or parts replacement
by other than authorized representative of
Yokogawa Electric Corporation is prohibited and
will void KEMA Intrinsically safe Certification.
Note 5. Special Conditions for Safe Use
• In the case where the enclosure of the Pressure
Transmitter is made of aluminium, if it is mounted
in an area where the use of category 1 G apparatus
is required, it must be installed such, that, even in
the event of rare incidents, ignition sources due to
impact and friction sparks are excluded.
Transmitter
Supply
Safety Barrier
Nonhazardous Location
[Installation Diagram]
Hazardous Location
+
–
+
–
F0306E.EPS
(*1)
Note 1
Sensor out
RTD sensor
Note 2
Without pulse output
With pulse output
Transmitter
Supply
Safety Barrier
Nonhazardous Location
Hazardous Location
+
–
+
–
+
(*1)
Note 1
Sensor out
RTD sensor
Note 2
Safety Barrier
+
–
(*1)
Note 1
Pulse
Note 1:
• In any safety barriers used the output current must
be limited by a resistor “R” such that Imaxout-Uz/
R.
• The safety barrier shall be certified by notify body
EU as ATEX.
• When using non isolation barrier, connect (*1) to
IS earthing system.
Note 2.
• RTD sensor is prepared by the user.
• The sensor signal line must withstand a test voltage
of 500 V AC.
• External temperature input code -4 is not appli-
cable.
(2) Electrical Connection
A mark indicating the electrical connection type is
stamped near the electrical connection port. These
marks are as followed.
T0301E.EPS
F0310E.EPS
Location of the mark
(3) Installation
WARNING
• All wiring shall comply with local installation
requirements and the local electrical code.
• There is no need for conduit seal in Division 1
and Division 2 hazardous locations because
this product is sealed at the factory.
(4) Operation
WARNING
• OPEN CIRCUIT BEFORE REMOVING
COVER. INSTALL IN ACCORDANCE WITH
THIS USER’S MANUAL
• Take care not to generate mechanical sparking
when access to the instrument and peripheral
devices in a hazardous location.
(5) Maintenance and Repair
WARNING
The instrument modification or parts replacement
by other than an authorized Representative of
Yokogawa Electric Corporation is prohibited and
will void the certification.