IM 01C25R01-01E
2-5
2. About Multivariable Transmitter
Table 2.2 Symbols
T0202E.EPS
#
Nc
Qm
Qv
Qv_norm
1
Symbol
2
6
8
7
5
3
4
SPb
T
Tb
SP
norm
Temp K1
b
ε
Kfactor
C
9
d
∆
p
Reference temperature unit: K
Diameter of orifice
Diameter Ratio
Expansion Factor
Base Density on Tb, SPb Condition
Density on Normal, Standard condition
Differential Pressure
(Transmitter Setting unit)
10
Basic flow Calculation factor
Volume Flow
Mass Flow
Description
Normal·Standard Volume Flow
Temperature unit: K
Unit convert factor
Discharge Coefficient
13
14
16
15
12
11
K
Compressibility factor
The density rate of change per temperature
1degC of a density base value (value which
set 100% to 1)
For volume flow: set 0.
Static Pressure unit: kPa abs
17
18
Reference static pressure unit: kPa abs
Flow Unit Category
Table 2.3 Mass Flow Unit (HART protocol type)
-
T0203E.EPS
Unit
LCD
Communication
grams per second
g/s
←
grams per minute
g/m
g/min
grams per hour
g/h
←
kilograms per second
kg/s
←
kilograms per minute
kg/m
kg/min
kilograms per hour
kg/h
←
kilograms per day
kg/d
←
metric tons per minute
t/m
t/min
metric tons per hour
t/h
←
metric tons per day
t/d
←
pounds per second
lb/s
←
pounds per minute
lb/m
lb/min
pounds per hour
lb/h
←
pounds per day
lb/d
←
short tons per minute
STon/m
STon/min
short tons per hour
STon/h
←
short tons per day
STon/d
←
long tons per hour
LTon/h
←
long tons per day
LTon/d
←
Table 2.4 Normal•Standard Volume Flow Unit
(HART protocol type)
T0204E.EPS
Unit
LCD
Communication
normal cubic meter per hour
Nm3/h
←
normal liter per hour
NL/h
←
Standard cubic feet per minute
SCFM
←
Table 2.5 Volume Flow Unit (HART protocol type)
T0205E.EPS
Unit
LCD
Communication
cubic feet per minute
CFM
←
gallons per minute
GPM
←
liters per minute
imperial gallons per minute
cubic meter per hour
gallons per second
liters per second
cubic feet per second
cubic feet per day
cubic meters per second
cubic meters per day
imperial gallons per hour
imperial gallons per day
cubic feet per hour
cubic meters per minute
barrels per second
barrels per minute
barrels per hour
barrels per day
gallons per hour
imperial gallons per second
liters per hour
gallons per day
million gallons per day
million liters per day
L/m
IGal/m
M3/h
gal/s
Mgal/d
L/s
CFS
ft3/d
M3/s
M3/d
IGal/h
IGal/d
CFH
m3/m
bbl/s
bbl/m
bbl/h
bbl/d
gal/h
IGal/s
L/h
gal/d
ML/d
L/min
ImpGal/min
←
←
←
←
←
←
←
←
ImpGal/h
ImpGal/d
←
m3/min
←
bbl/min
←
←
←
ImpGal/s
←
←
←
2.5.1 Configuration Procedure for Basic
Mode
Either a communicator or the mass flow configuration
software is required to carry out configuration in basic
mode.
Calculation of the basic mode parameters is necessary
to perform configuration. Following shows the proce-
dures for HART protocol type.
(1) Have ready a power supply, a personal computer, a
HART modem and the FSA210 mass flow configu-
ration software.
(2) Install the flow configuration software on the
personal computer.
This is not necessary if only the HART communi-
cator is used for configuration.