![YOKOGAWA Dpharp EJX910A User Manual Download Page 92](http://html1.mh-extra.com/html/yokogawa/dpharp-ejx910a/dpharp-ejx910a_user-manual_911714092.webp)
IM 01C25R03-01E
A-21
APPENDIX 3. INPUT SELECTOR (IS) BLOCK
APPENDIX 3. INPUT SELECTOR (IS) BLOCK
The function of the Input Selector (IS) block is to automatically select one signal from multiple input signals using a
specified selection method.
The IS block is used for selective control in which one measured quantity is selected from multiple measured quanti-
ties to be transmitted to the controller as a controlled variable. This feature is primarily used for temperature control
systems.
A3.1 Input Selector Function Block Schematic
The following shows the Input Selector function block schematic.
IN_1
First Good
SELECTION
MINIMUM
MAXIMUM
MIDDLE
Configuration
Auto
Man
MODE
SELECTED
OUT
STATUS_OPTS
SELECT_TYPE
MIN_Good
AVERAGE
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
DISABLE_1
DISABLE_2
DISABLE_3
DISABLE_4
DISABLE_5
DISABLE_6
DISABLE_7
DISABLE_8
OP_SELECT
FA0301.EPS
Figure A3.1 IS Block
Input Parameters (Input Terms)
IN_1
: Block input 1
IN_2
: Block input 2
IN_3
: Block input 3
IN_4
: Block input 4
IN_5
: Block input 5
IN_6
: Block input 6
IN_7
: Block input 7
IN_8
: Block input 8
DISABLE_1 : Selector switch 1 to disable input 1 from being selected
DISABLE_2 : Selector switch 2 to disable input 2 from being selected
DISABLE_3 : Selector switch 3 to disable input 3 from being selected
DISABLE_4 : Selector switch 4 to disable input 4 from being selected
DISABLE_5 : Selector switch 5 to disable input 5 from being selected
DISABLE_6 : Selector switch 6 to disable input 6 from being selected
DISABLE_7 : Selector switch 7 to disable input 7 from being selected
DISABLE_8 : Selector switch 8 to disable input 8 from being selected
OP_SELECT : A parameter which can be set by an operator to forcibly employ the input of the selected number