![YOKOGAWA Dpharp EJX910A User Manual Download Page 74](http://html1.mh-extra.com/html/yokogawa/dpharp-ejx910a/dpharp-ejx910a_user-manual_911714074.webp)
IM 01C25R03-01E
A-3
APPENDIX 1. SIGNAL CHARACTERIZER (SC) BLOCK
A1.2 Input Section
The input section determines the mode and judges BLOCK_ERR.
A1.2.1 Determining the Mode
The following describes operations of the Signal Characterizer block.
O/S
(Out of Service)
• System-stopped status
• Configuration change
Supported Mode
Rules
Man
• If you do not want to output the value and the status from IN, you can manually
transmit the value to OUT.
Auto
• Automatic system operation status
TA0102.EPS
A1.2.2 Judging BLOCK_ERR
BLOCK_ERR indicates the cause of an error in the function block. If the cause of an error indicated by
BLOCK_ERR occurs, the following configuration error is generated.
Block Configuration Error
1) "
INFINITY" has been configured for CURVE_X and CURVE_Y.
2) "+INFINITY" has been configured for X1 of CURVE_X.
3) "+INFINITY" has been configured for Y1 of CURVE_Y.
4) A value of the array of CURVE_X does not increase in a monotone manner.
5) A configuration error when SWAP_2 is on
• A value of the array of CURVE_Y does not increase or decrease in a
monotone manner.
6) The value of SWAP_2 is any value other than 1 or 2.
Name
Description
TA0103.EPS
The mode changes to O/S if a block configuration error occurs.