IM 01C25R03-01E
10-1
10. GENERAL SPECIFICATIONS
10. GENERAL SPECIFICATIONS
10.1 Standard specifications
For items other than those described below, refer to
each User’s Manual.
Applicable Model:
EJX910A
Output:
Digital communication signal based on FOUNDATION
Fieldbus protocol.
Supply Voltage:
9 to 32 V DC for general use, flameproof type and Type n
Communication Requirements:
Supply Voltage: 9 to 32 V DC
Current Draw (Stedy state): 15 mA (max)
Current Draw (Software Download state): 24 mA (max)
Response Time (for Primary Value)
M, H capsule: 300 msec
When amplifier damping is set to zero, and including dead
time.
Update Period:
Differential Pressure: 200 msec
Static Pressure: 200 msec
Capsule Temperature: 1 sec
Amplifier Temperature: 1 sec
External Temperature output: 800 msec
Integral Indicator (LCD display)
5-digit Numerical Display, 6-digit Unit Display and Bar
graph. The indicator is configurable to display one or up to
four of the I/O signals periodically.
Functional Specifications:
Functional specifications for Fieldbus communication
conform to the standard specifications (H1) of
FOUNDATION Fieldbus.
Function Block:
T1001.EPS
Number
Execution
time
Block
name
AI
30 mS
5
For differential pressure, static
pressure and temperature
SC
30 mS
1
An Output of Signal Characterizer
block is a non-linear function of
the respective input. The function
is determined by a table
IT
30 mS
1
Integrator block integrates a
variable as a function of the time
or accumulates the counts
IS
30 mS
1
Input Selector block provides
selection of up to eight inputs
and generate an output based
on the configured action
AR
30 mS
1
Arithmetic block permits simple
use of popular measurement
math functions
Applicable when LC1 option is
specified
Note
45 mS
PID
1
LM Function:
LM function is supported.
LM function is disabled when shipped.
10.2 Optional specifications
For items other than those described below, refer to each User’s Manual.
T1003.EPS
Description
PID control function
Software damping
Based on Fieldbus Foundation Specification (FF-883)
Download class: Class1
Code
LC1
CC
EE
Item
PID function
Data configuration at
factory
Software Download
Function