IM 01C25R03-01E
9-5
9. PARAMETER LISTS
T0902-3.EPS
Write
Mode
Explanation
Factory
Default
Relative
Index
Parameter Name
Index
2043
CAL_SP_
DEVIATION_LO
O/S
0
43
Deviation value for zero adjustment of static pressure
2044
SP_VALUE_FTIME
O/S
1
44
Damping time constant for static pressure
2045
ATM_PRESS
O/S
101.325
45
Atmosphere pressure value used to obtain gauge pressure
value from absolute pressure.
2046
CURRENT_ATM_
PRESS_ENABLE
O/S
0
46
Automatically sets the L-side static pressure value to the
atmospheric pressure value (ATM_PRESS).
2047
EXT_TEMP_VAL
–
47
Indicates the external temperature value and status.
2048
EXT_TEMP_
RANGE
–
-200-
850
°
C
48
Indicates the external temperature sensor range, unit and
decimal point.
2049
CAL_EXT_TEMP_
POINT_HI
O/S
100
49
This is High-side adjustment value. Adjust this value so that
the current external temperature becomes this setting value.
2050
CAL_EXT_TEMP_
POINT_LO
O/S
0
50
This is Low-side adjustment value. Adjust this value so that
the current external temperature becomes this setting value.
2051
CAL_EXT_TEMP_
MIN_SPAN
–
10.0
51
Indicates the minimum span of the external temperature.
2052
CAL_EXT_TEMP_
UNIT
–
1001
52
Indicates the calibration unit of the external temperature
sensor.
2053
CAL_EXT_TEMP_
DEVIATION_HI
O/S
0
53
This is the adjustment coefficient for performing span
adjustment of the external temperature.
2054
CAL_EXT_TEMP_
DEVIATION_LO
O/S
0
54
This is the adjustment coefficient for performing zero
adjustment of the external temperature.
2055
EXT_TEMP_
VALUE_FTIME
O/S
1.0
55
Sets the primary filter time constant (unit: seconds) of the
external temperature.
2057
FIXED_EXT_
TEMP_VALUE
O/S
20.0
57
Sets the external temperature fixed value.
2058
SIMULATE_
MODE
AUTO
0
58
This is the switch for enabling simulation.
0=Simulation OFF
1=Differential pressure signal simulation ON
2=Static pressure signal simulation ON
3=Differential pressure static pressure signal simulation ON
4=External temperature signal simulation ON
5=Differential pressure external temperature signal
simulation ON
6=Static pressure external temperature signal simulation
ON
7=Differential pressure static pressure external
temperature signal simulation ON
15=Differential pressure static pressure external
temperature signal (without damping processing) simulation ON
2056
EXT_TEMP_
OPTS
O/S
0
56
Selects the external temperature selection operation.
0=No Selection OFF (output of external temperature)
1=Yes Selection ON (output of FIXED_EXT_TEMP_VALUE)
2=Fall Back Selection at broken wire (output of
FIXED_EXT_TEMP_VALUE at broken wire)
2037
SP_VALUE_
RANGE
–
Range of
capsule
37
High and low range limit values, engineering units, and
decimal point place for static pressure.
2038
CAL_SP_
POINT_HI
O/S
25
38
The highest calibrated value for static pressure
2039
CAL_SP_
POINT_LO
O/S
0
39
The Lowest calibrated value for static pressure
2040
CAL_SP_MIN_
SPAN
–
1.0
40
The minimum calibration span allowed for static pressure
2041
CAL_SP_UNIT
–
1545 (MPaa)
41
The calibrated engineering unit for static pressure. This unit is
linked to XD_SCALE.unit of AI blocks
2042
CAL_SP_
DEVIATION_HI
O/S
0
42
Deviation value for span adjustment of static pressure