Section H: Control Circuit Terminals
H1 Digital Inputs
· Local/Remote Selection (setting: “1”)
Selects the operation mode, only when the inverter is stopped.
Local:
Operation according to frequency reference and run command from digital operator.
Remote: Operation according to frequency reference and run command set by B1-01 and B1-
02, respectively.
Note:
When local/remote selection is set by a multi-function contact input terminal, local/remote
selection from the digital operator key is disabled.
· Option/Inverter Selection (setting: “2”)
Selects whether operation is performed using a reference command from an option card or from the
inverter. Selection is effective only when the inverter is stopped.
Open:
Runs by frequency reference and run command from inverter control circuit termi-
nal or digital operator.
Closed:
Runs by frequency reference and run command from an option card.
Multi-Step Ref 1 through 3 and Jog Freq Ref (Set value = 3, 4, 5, and 6)
O - Open
X - Closed
-- Has no effect
d1-01 is effective when b1-01 is set to 0 (reference from the digital operator)
d1-02 is effective when the terminal 16 setting (H3-05) is set to anything other than zero.
Terminal 8
Terminal 7
Terminal 6
Terminal 5
(H1-06 = 6)
(H1-05 = 5)
(H1-04 = 4)
(H1-03 = 3)
Preset
Jog Freq Ref
Multi-Step Ref 3
Multi-Step Ref 2
Multi-Step Ref 1
Reference
O
O
O
O
Reference 1 (d1-01)
O
O
O
X
Reference 2 (d1-02)
O
O
X
O
Reference 3 (d1-03)
O
O
X
X
Reference 4 (d1-04)
O
X
O
O
Reference 5 (d1-05)
O
X
O
X
Reference 6 (d1-06)
O
X
X
O
Reference 7 (d1-07)
O
X
X
X
Reference 8 (d1-08)
X
Jog Reference (d1-09)