VS-616G5 Programming Manual
15
V/f
V/f w/PG Open Loop
Vector
Flux
Vector
During flux vector control, select an operation mode to be employed when the frequency reference (ana-
log input) drops below the minimum output frequency (El -09). During V/f or open loop vector control,
baseblock is applied when the output frequency drops below the minimum output frequency (El -09).
This parameter selects the microprocessor scan time for reading sequence input data from the control
circuit terminals.
Set to “0” when a quicker response is needed from the control circuit terminals.
Parameter b1-07 determines how the inverter will function when switching between local and remote
operation. This function prevents the motor from running when switching between local/remote and
the inverter is controlled from the digital operator.
B1-05 Operation Selection at Zero Speed
Zero Speed Oper
-
-
-
A
Setting
Description
0
E1 -09
disabled, run according to frequency reference (factory default)
1
Baseblock
2
Run at minimum output frequency (E1-09)
3
Zero-speed operation (internal speed reference is set to “0”)
B1-06 Input Scan Time
Cntl Input Scans
B
B
B
B
Setting
Description
0
2ms scan time for 2 scans
1
5ms scan time for 2 scans (factory default)
B1-07 Operation Selection After Switch to Remote Mode LOC/REM RUN Sel
A
A
A
A
Setting
Description
0
(Cycle Extrn RUN) - If the run command is closed when switching from local control to remote control,
the inverter will not run.
The run command must be cycled for the inverter to run. (factory default)
1
(Accept Extrn RUN) - If the run command is closed, when switching from local control to remote con-
trol, the inverter will run.
Section B: Application Parameters
B1 Sequence