VS-616G5 Programming Manual
75
V/f
V/f w/PG Open Loop
Vector
Flux
Vector
The setting of parameter F9-03 selects the stopping method when an EF0 fault is detected.
Setting Range:
0-60000
Factory Default:
0
Parameter F9-04 sets the trace sample time when using the CP-916B option card.
Parameter F9-05 allows the CP-916 option card to set the torque limits when the inverter is in the
speed control mode and the torque reference when operating in the torque control mode
Operation Truth Table for Parameter F9-05
Note: The inverter will use the lowest value from the CP-916, L7-01 to L7-04, or the multi-function
analog input terminals 14 or 16.
F9-03 Option External Fault Action
EFO Fault Action
A
A
A
A
Setting
Description
0
Ramp to stop according to C1-02 set value.
1
Coast to stop. (factory setting)
2
Ramp to stop according to C1-09 set value.
3
Alarm flashes, operation continues.
F9-04 Trace Sample Time
Trace Sample Tim
A
A
A
A
F9-05 Torque Reference/Torque Limit Select (CP-916)
Torq Ref/Lmt Sel
-
-
-
A
Setting
Description
0
Disabled -Torque reference/torque limits set by G5 pro-
gram parameters or by analog input.
1
Enabled - Torque reference/torque limits set by G5 pro-
gram parameters, analog input, or by the CP-916. (factory
default)
Set Value
Speed Control (Torque Limit)
Torque Control (Torque Reference)
F9-05 = 0 Set by parameter or analog input.
Set by analog input terminal 14 or 16.
F9-05 = 1 Set by CP-916 option card, parameter, or analog
input.
Set by CP-916 option card.
Section F: Option Parameters
F9 CP-916
Option Set-up