VS-616G5 Programming Manual
149
G
ro
up
H
T
er
m
in
al
F
un
ct
io
n
Fu
nc
tio
n
H
4
An
al
og
O
ut
pu
ts
H4-01
Monitor Selection
Terminal 21
(Terminal 21 Sel)
1~38
1
2
Analog output selection (terminal
21 (same as F4-01)
1: Frequency reference
2: Output frequency
3: Inverter output current
5: Motor speed
6: Output voltage
7: DC bus voltage
8: Output power
9: Torque reference (internal)
15: External terminal 13 input
voltage
16: External terminal 14 input
voltage
17: External terminal 16 input
voltage
18: Motor secondary current (Iq)
19: Motor excitation current (Id)
20: Primary frequency after SFS
21: Speed controller ASR input
22: Speed controller ASR output
23: Speed deviation
24: PID feedback
26: Voltage reference (Vq out-
put)
27: Voltage reference (Vd out-
put)
31: Not Used
32: ACR (q) Output
33: ACR (d) Output
36: PID Input
<1110>
37: PID Output
<1110>
38: PID Reference
<1110>
x
B
B
B
B
H4-02
Terminal 21 Output
Gain
(Terminal 21 Gain)
0.00~
2.50
0.01
1.00
—
o
B
B
B
B
H4-03
Terminal 21Output
Bias
(Terminal 21 Bias)
–10.0~
+10.0
0.0%
0.0
—
o
B
B
B
B
H4-04
Terminal 23
Monitor
(Terminal 23 Sel)
1~38
1
3
Analog output selection (terminal
23) (same as H4-01)
x
B
B
B
B
H4-05
Terminal 23 Output
Gain
(Terminal 23 Gain)
0.00~
2.50
0.01
0.50
—
o
B
B
B
B
H4-06
Terminal 23 Output
Bias
(Terminal 23 Bias)
–10.0~
+10.0
0.1%
0.0
—
o
B
B
B
B
H4-07
Analog Output
Signal Selection
(AO Level Select)
0, 1
1
0
0: (0 - +10 VDC)
1: (–10V +10 VDC)
x
B
B
B
B
Function
Parameter
No.
Name
(Digital Operator
Display)
Setting
Range
Setting
Unit
Factory
Setting
Remarks
(Digital Operator Display)
Change
during
Operation
o: Enabled
x: Disabled
Parameter Access Level
User
Setting
V/f
V/f
w/
PG
Open
Loop
Vector
Flux
Vector
Appendix