VS-616G5 Programming Manual
Section H: Control Circuit Terminals
H1 Digital Inputs
· Terminal 13/14 Selection (setting: “1F”)
Open:
Terminal 13 is used for the master frequency reference.
Closed:
Terminal 14 is used for the master frequency reference.
Note:
When the set value of Terminal 14 Selection (H3-09) is other than “1F” and the contact input
is set for terminal 13/14 selection (H1-__ = “1F”), a setting error (OPE3) occurs.
· External Fault (setting: “20-2F”)
Use this contact input to select how the inverter responds to an external fault.
Notes:
1. N.O. = normally open contact; N.C. = normally closed contact
2. Setting “24” is the factory default.
3. Set up the external fault function according to the following tree:
External Fault Selection
Setting
Result
Input Level Selection
Detection Method
External Fault Action
N.O.
N.C.
Always During Run Ramp to Stop Coast to Stop
Fast-stop
Alarm Only
√
√
√
20
√
√
√
24
√
√
√
28
√
√
√
2C
√
√
√
22
√
√
√
26
√
√
√
2A
√
√
√
2E
√
√
√
21
√
√
√
25
√
√
√
29
√
√
√
2D
√
√
√
23
√
√
√
27
√
√
√
2B
√
√
√
2F