VS-616G5 Programming Manual
Section E: Motor Parameters
E2 Motor 1 Set-up
Sets the motor leakage inductance in units of 0.1%. The default setting varies depending on the
inverter model setting (O2-04).
Setting Range:
0.00 to 1.00
Factory Default:
0.5
Sets the motor iron core saturation coefficient at 50% of the magnetic flux. This parameter is set auto-
matically during auto-tuning, so it does not need to be changed.
Setting Range:
0.00 to 1.00
Factory Default:
0.75
Sets the motor iron core saturation coefficient at 75% of the magnetic flux. This parameter is set auto-
matically during auto-tuning, so it does not need to be changed.
Setting Range:
0.0 to 10.0%
Factory Default:
0.0%
Sets the motor mechanical loss as a percentage of motor rated output power, in units of 0.1%.
Setting Range:
0 to 65535
Factory Default:
14 (Factory default depends on inverter capacity.)
This parameter sets the motor iron loss of the torque compensation.
E2-06 Leakage Inductance
Leak Inductance
−
−
A
A
E2-07 Core-Saturation Compensation Coefficient 1
Saturation Comp1
−
−
A
A
E2-08 Core-Saturation Compensation Coefficient 2
Saturation Comp2
−
−
A
A
E2-09 Motor Mechanical Loss
Mechanical Loss
−
−
−
A
E2-10 Motor Iron Loss Torque Compensation
<1110>
Tcomp Iron Loss
A
A
−
−