User Parameter Tables
4
-
23
4
Option Parameters: F
PG Option Setup: F1
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Register
Page
V/f
Open
Loop
Vector
Closed
Loop
Vector
Display
F1-01
PG constant
Sets the number of PG pulses
per revolution
0 to
60000
1024
No
No
No
Q
380H
5-63
PG Pulses/
Rev
F1-02
Operation
selection at
PG open cir-
cuit (PGO)
Sets the PG disconnection
stopping method.
0: Ramp to stop (Deceleration
to stop using the
deceleration time 1, C1-
02.)
1: Coast to stop
2: Fast stop (Emergency stop
using the deceleration time
in C1-09.)
3: Continue operation (To
protect the motor or
machinery, avoid to use
this setting.)
0 to 3
1
No
No
No
A
381H
5-63
PG Fdbk
Loss Sel
F1-03
Operation
selection at
overspeed
(OS)
Sets the stopping method when
an overspeed (OS) fault
occurs.
0: Ramp to stop (Deceleration
to stop using the
deceleration time 1, C1-
02.)
1: Coast to stop
2: Fast stop (Emergency stop
using the deceleration time
in C1-09.)
3: Continue operation (To
protect the motor or
machinery, avoid to use
this setting.)
0 to 3
1
No
No
No
A
382H
5-63
PG Over-
speed Sel
F1-04
Operation
selection at
deviation
Sets the stopping method when
a speed deviation (DEV) fault
occurs.
0: Ramp to stop (Deceleration
to stop using the
deceleration time 1, C1-
02.)
1: Coast to stop
2: Fast stop (Emergency stop
using the deceleration time
in C1-09.)
3: Continue operation (DEV
is displayed and operation
continued.)
0 to 3
3
No
No
No
A
383H
5-63
PG
Deviation Sel
F1-05
PG rotation
0: Phase A leads with forward
run command. (Phase B
leads with reverse run
command.)
1: Phase B leads with forward
run command. (Phase A
leads with reverse run
command.)
0 or 1
0
No
No
No
Q
384H
5-63
PG Rotation
Sel