User Parameter Tables
4
-
43
4
o2-02
STOP key
during con-
trol circuit
terminal
operation
Enables/Disables the Stop key
in the run mode.
0: Disabled (When the run
command is issued from an
external terminal, the Stop
key is disabled.)
1: Enabled (Effective even
during run.)
0 or 1
0
No
A
A
A
506H
5-55
Oper Stop
Key
o2-03
User parame-
ter initial
value
Clears or stores user initial val-
ues.
0: Stores/not set
1: Begins storing (Records the
set parameters as user
initial values.)
2: All clear (Clears all
recorded user initial values)
When the set parameters are
recorded as user initial values,
1110 will be set in A1-03.
0 to 2
0
No
A
A
A
507H
5-55
User
Defaults
o2-04
kVA selec-
tion
Do not set unless after replac-
ing the control board. (Refer to
page 5-60
for the setting val-
ues).
0 to FF
0
No
A
A
A
508H
5-55
Inverter
Model#
o2-05
Frequency
reference set-
ting method
selection
When the frequency reference
is set on the Digital Operator/
Monitor frequency reference
monitor, sets whether the Enter
key is necessary or not.
0: Enter key needed
1: Enter key not needed
When set to 1, the Inverter
accepts the frequency refer-
ence without Enter key opera-
tion.
0 or 1
0
No
A
A
A
509H
5-55
Operator
M.O.P.
o2-06
Operation
selection
when digital
operator is
disconnected
Sets the operation when the
Digital Operator/Monitor is
disconnected.
0: Operation continues even if
the Digital Operator/Moni-
tor is disconnected.
1: OPR is detected at Digital
Operator/Monitor
disconnection. Inverter
output is switched off, and
the fault contact is
operated.
0 or 1
0
No
A
A
A
50AH
5-27
Oper
Detection
o2-07
Cumulative
operation
time setting
Sets the cumulative operation
time in hour units.
0 to
65535
0 hr
No
A
A
A
50BH
5-55
Elapsed Time
Set
o2-08
Cumulative
operation
time selec-
tion
0: Accumulated inverter
power on time.
1: Accumulated inverter run
time.
0 or 1
0
No
A
A
A
50CH
5-55
Elapsed Time
Run
o2-09
Initialize
Mode
0: Asia
1: America
2: Europe
0 to 2
0
No
A
A
A
50DH
-
InitModeSet
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Register
Page
V/f
Open
Loop
Vector
Closed
Loop
Vector
Display