User Parameter Tables
4
-
61
4
400 V Class Inverters
Parameter
Number
Name
Unit
Factory Setting
-
Inverter Capacity
kW
3.7
4.0
5.5
7.5
11
15
o2-04
kVA selection
-
4
5
5
6
7
8
E2-01
(E4-01)
Motor rated current
A
7.00
7.00
9.80
13.30
19.9
26.5
E2-02
(E4-02)
Motor rated slip
Hz
2.70
2.70
1.50
1.30
1.70
1.60
E2-03
(E4-03)
Motor no-load current
A
2.30
2.30
2.60
4.00
5.6
7.6
E2-05
(E4-05)
Motor line-to-line resistance
W
3.333
3.333
1.595
1.152
0.922
0.550
E2-06
(E4-06)
Motor leak inductance
%
19.3
19.3
18.2
15.5
19.6
17.2
E2-10
Motor iron loss for torque
compensation
W
130
130
193
263
385
440
L8-02
Overheat pre-alarm level
°
C
90
90
85
90
73
90
Parameter
Number
Name
Unit
Factory Setting
-
Inverter Capacity
kW
18.5
22
30
37
45
55
o2-04
kVA selection
-
4
5
6
7
8
9
E2-01
(E4-01)
Motor rated current
A
32.9
38.6
Development
E2-02
(E4-02)
Motor rated slip
Hz
1.67
1.70
E2-03
(E4-03)
Motor no-load current
A
7.8
9.2
E2-05
(E4-05)
Motor line-to-line resistance
W
0.403
0.316
E2-06
(E4-06)
Motor leak inductance
%
20.1
23.5
E2-10
Motor iron loss for torque
compensation
W
508
586
L8-02
Overheat pre-alarm level
°
C
80
80
http://nicontrols.com