10 Input Assemblies (Drive Produces)
44
YASKAWA ELECTRIC
SIEP YEACOM 01A V1000 Option EtherNet/IP Technical Manual
Torque Reference
Not Supported on V1000
PG Count Value
Contained MEMOBUS/Modbus Address
Frequency Command
Monitor parameter U1-01
Output Frequency
Actual Drive Speed
Monitors drive output frequency.
Unit depends on o1-03.
Unit is not affected by Speed Scale SS.
Output Current
Actual Output Current
Monitors drive output current.
Unit is 0.01 A
Unit is not affected by Current Scale CS.
INV Terminal A1 Input
MEMOBUS/Modbus (0x46)
Monitor parameter U1-13
Main DC Voltage
Main Circuit DC Voltage
Monitor parameter U1-07
Error Code
U2-01 converted using fault code table
F7-33 Alarm Code
Programmable: MEMOBUS/Modbus (0x7F)
F7-34 Output Power
Programmable: MEMOBUS/Modbus (0x47)
Monitor parameter U1-08
F7-35 Terminal A2 Input
Programmable: MEMOBUS/Modbus (0x4F)
Monitor parameter U1-14
F7-36 INV Terminal 1-12
Programmable: Only 1 - 7 available on V1000, MEMOBUS/Modbus (0x49)
Monitor parameter U1-10
F7-37 Terminal A3 Input
Programmable: MEMOBUS/Modbus (0x50)
Monitor parameter U1-15, not supported on V1000
F7-38 PG Count Value (CH 2)
Programmable: MEMOBUS/Modbus (0xF1)
Serial interface Control Response
F7-39 NetRef (Status)
Status of reference command from Network
0: Reference command is not from network
1: Reference command is from network
F7-40 Drive Software Version
Programmable: MEMOBUS/Modbus (0x4D)
Monitor parameter U1-25
Parameter
Data