4.3 Wiring the Power Supply to the SERVOPACK
4.3.5 Wiring Regenerative Resistors
4
W
iring and Connecting
S
ER
VOP
ACK
s
4-23
2.
Connect the External Regenerative Resistor between the B1/
⊕
and B2 terminals.
3.
Set Pn600 (Regenerative Resistor Capacity) and Pn603 (Regenerative Resistance).
Refer to the following section for details on the settings.
5.19 Setting the Regenerative Resistor Capacity
SERVOPACK Models SGD7S-470A, -550A, -590A, and -780A
1.
Connect the R1 and R2 terminals on the Regenerative Resistor Unit to the B1/ and B2
terminals on the SERVOPACK.
2.
Set Pn600 (Regenerative Resistor Capacity) and Pn603 (Regenerative Resistance) as
required.
•
When using the Yaskawa-recommended Regenerative Resistor Unit, use the default settings for
Pn600 and Pn603.
•
If you use any other external regenerative resistor, set Pn600 and Pn603 according to the specifica-
tions of the regenerative resistor.
Refer to the following section for details on the settings.
Setting the Regenerative Resistor Capacity
Enlarged View