7-24
Registers
Drive Parameter Registers (Read/Write) (continued)
REGISTER PARAMETER
PARAMETER
PARAMETER
LIMITS / DESCRIPTION
INITIAL
(in hex)
FUNCTION
SETTING
VALUE
48Dh
L3-06
Stall Prevention Level during Running
30 to 200%
160
48E-48Fh
Reserved
490h
L4-01
Speed Coincidence Frequency
0.0 to 400.0 Hz
0.0
491h
L4-02
Speed Coincidence Width
0.0 to 20.0 Hz
2.0
492h
L4-03
Speed Coincidence Frequency (+/-)
-400.0 to +400.0 Hz
0.0
493h
L4-04
Speed Coincidence Width (+/-)
0.0 to 20.0 Hz
2.0
494h
L4-05
Frequency Reference Loss
0
Stop
0
Detection
1
Run at 80% of Frequency Reference
495h
L5-01
Number of Auto Restart Attempts
0 to 10
0
496h
L5-02
Auto Restart Operation Selection
0
No Fault Relay
0
1
Fault Relay Active
497h
L5-03
Fault Restart Time
0.5 to 180.0 seconds
10.0
498h
L6-01
Torque Detection Selection 1
0
Disabled
1
Detected during Speed Agree
(operation continues)
2
Detected during Running (operation
continues)
0
3
Detected during Speed Agree (drive
faults)
4
Detected during Running (drive faults)
499h
L6-02
Torque Detection Level 1
0 to 300%
150
49Ah
L6-03
Torque Detection Time 1
0.0 to 10.0 seconds
0.1
49Bh
L6-04
Torque Detection Selection 2
0
Disabled
1
Detected during Speed Agree
(operation continues)
2
Detected during Running (operation
continues)
0
3
Detected during Speed Agree (drive
faults)
4
Detected during Running (drive faults)