7-5
Registers
Monitor Registers (continued)
REGISTER
FUNCTION
BIT
DESCRIPTION
(in hex)
NO.
015h
Fault Content 2
0
External Fault 3 (EF3)
1
External Fault 4 (EF4)
2
External Fault 5 (EF5)
3
External Fault 6 (EF6)
4
External Fault 7 (EF7)
5
External Fault 8 (EF8)
6
not used
7
Overspeed (oS)
8
Speed Deviation (DEV)
9
PG Open (PGo)
10
Input Phase Loss (PF)
11
Output Phase Loss (LF)
12
DCCT Fault (CF)
13
Operator Disconnected (OPR)
14
EEPROM Write-in Fault (ERR)
15
not used
016h
Fault Content 3
0
Modbus Communication Error (CE)
1
not used
2
not used
3
not used
4
Control Fault (CF)
5
Zero Servo Fault (SVE)
6-15
not used
017h
CPF Content 1
0
not used
1
not used
2
CPF02 Fault
3
CPF03 Fault
4
CPF04 Fault
5
CPF05 Fault
6
CPF06 Fault
7-15
not used
Summary of Contents for GPD 515/G5 Modbus RTU
Page 1: ...GPD 515 G5 Modbus RTU Technical Manual ...
Page 24: ...6 4 The Message Format ...
Page 30: ...6 10 The Message Format ...