7-23
Registers
Drive Parameter Registers (Read/Write) (continued)
REGISTER PARAMETER
PARAMETER
PARAMETER
LIMITS / DESCRIPTION
INITIAL
(in hex)
FUNCTION
SETTING
VALUE
480h
L1-01
Motor Overload Protection
0
Disabled
1
Selection
1
Enabled
481h
L1-02
Motor Overload Protection Time
Constant
0.1 to 5.0 minutes
1.0
482h
L2-01
Momentary Power Loss
0
Disabled
Detection Selection
1
Power Loss Ride-thru
0
2
CPU Power Active
483h
L2-02
Momentary Power Loss Ride-thru Time
0.0 to 2.0 seconds
(1)
484h
L2-03
Momentary Power Loss Minimum
Base Block Time
0.0 to 5.0 seconds
(1)
485h
L2-04
Momentary Power Loss Recovery
Ramp Time
0.0 to 2.0 seconds
0.3
486h
L2-05
Undervoltage Detection Level
150 to 210V (230V unit)
300 to 420V (460V unit)
190
380
487h
L2-06
KEB Frequency
0.0 to 100.0%
0.0
488h
L3-01
Stall Prevention Selection during
0
Disabled
Acceleration
1
General-purpose
1
2
Intelligent (2)
489h
L3-02
Stall Prevention Level during Accel
0 to 200%
170
48Ah
L3-03
Stall Prevention Level during Accel
(CHP)
0 to 100%
(3)
48Bh
L3-04
Stall Prevention Selection during
0
Disabled
Deceleration
1
General-purpose
1
2
Intelligent (2)
48Ch
L3-05
Stall Prevention Selection during
0
Disabled
Running
1
Decel time 1
1
2
Decel time 2
Notes (for this page only):
1. Initial value differs depending on drive capacity.
2. When Vector Control (A1-02 = 2 or 3) is selected, set value 2 (intelligent) cannot be used.
3. Initial value differs depending on control method (A1-02).